Superintend IMD
© Copyright Muuntosähkö Oy - Trafox
15
The following parameters can be changed in the Setup menu:
•
INSULATION LIMIT
: Alarm limit of the insulation resistance. If the measured
value is lower than the alarm limit, an alarm
is given. The setup range is 10…100
kΩ with 10 kΩ intervals and 100 kΩ…1,000 kΩ with 50 kΩ intervals.
Factory
default value is 100 kΩ.
•
PRE INSULATION LIMIT:
The pre-insulation limit of the insulation resistance.
Activates the INS. WARN. relay.
The setup range is 10…100 kΩ with 10 kΩ
intervals and 100 kΩ…1,000 kΩ with 50 kΩ intervals. Pre
-insulation limit is
allowed to be equal or higher than the alarm limit. Factory default value is 500
kΩ.
•
AUTOMATIC ALARM ACKNOWLEDGEMENT:
This setting determines whether
all the alarms shall be acknowledged automatically as soon as they are
deactivated.
•
Filter:
Not in use.
•
TIME:
The time and date of the real time clock.