© Copyright Muuntosähkö Oy
–
Trafox
Superintend IMD
ALARM MENU
The alarm menu has two levels. The menu level shows if the alarm is active (ALARM),
inactive but not acknowledged (OLD ALRM) or if the situation is normal (OK). The
screen mode shows the value, alarm limit and time of the parameter that caused the
alarm.
If the start-up delay has been enabled (SETUP
→
StDelay), the alarms cannot be
activated before the set start-up delay has been elapsed after powering on the unit.
An alarm always indicates that the fault in question is still active. An active fault cannot
be acknowledged until the issue that caused it has been fixed. The fixed fault is
acknowledged when its time is checked and the T button is pressed. The button takes
you back to the menu level without acknowledging the fault.
All fixed faults can also be acknowledged on one go by means of the Alarm reset function
in the Monitor menu.
If the automatic alarm acknowledgement has been enabled (SETUP
→
AutoRst), the faults
are acknowledged automatically as soon as they are fixed.