Superintend IMD
© Copyright Muuntosähkö Oy - Trafox
11
MONITOR MENU
The Monitor menu is the default menu of the IM-04DCCT unit during use. All modes of
the menu always return to the topmost item on the Monitor menu after 20 minutes from
the last press of a button.
The following measured parameters are available in the Monitor menu screen:
•
IT network’s insulation resistance and capacitance in relation to protective earth.
Displayed in kOhms and micro farads.
•
Time and date
•
All fixed alarms can be acknowledged on one go.
•
Firmware version
The default display is insulation resistance and capacitance. Other parameters and
functions can be viewed by using the button.
The system test is started from the Monitor menu by pressing T and then selecting Y in
the Start test menu and pressing T. This starts the test of the internal measurement
circuit of the IM-04DCCT unit. If the test is completed successfully, the screen displays
momentarily the text Test OK; otherwise the text shown in Test FAILED, and an
insulation fault alarm is given to indicate that the insulation resistance can no longer be
measured.