Ensure the correct measuring system has been programmed with the preset
SNN
before writing the
SNN
. Use one of the following verification options found under the program tab
Device ID
:
Displayed article number and serial number in the field
Device ID
and MAC address displayed in the
field
MAC address
. These data are noted on the nameplate of the measuring system.
The button
Identify
triggers the status LEDs of the relevant measuring system to flash, which
makes assignments simple and easy.
Execute the function
Apply
after verifying that the correct measuring system has being addressed.
The measuring system immediately applies these settings.
Several devices can be integrated into the LAN network via a switch if several devices have to be
programmed. Select the devices by entering the corresponding IP address in the
TR SNCT Device
Applet
.
Originators that support Type 1 SafetyOpen configurations can also program the
TUNID
. These originator devices support the “SNCT-to-Originator-to-Target”
configuration scheme.
The user must ensure the uniqueness of an automatically assigned
SNN
if an
originator programmed the
TUNID
with an automatic
SNN
setting function.