ECO 1-7639 060220 REV.- FORM: 8224
2 of 4
A. Cut out the required amout from the duct (see
INSTALL HotPod
TM
for dimensions).
B. MINIMUM 4 feet (122cm) from outlet register.
C. Wiring cover
D. Fasten with 3 sheet metal screws both ends.
E. Insert male crimped end.
F. Crimp the cut end.
G. Add vibration-damped supports at both ends.
POWER WIRING
Warning !
Remove power from 120Vac circuit selected. Do not energize circuit until all connections are made and HotPod
TM
wiring
enclosure is closed after installation.
FOR PERMANENT WIRED MODELS
1. Remove wiring cover. Following all local codes, connect to 120 Vac, 15 amp dedicated circuit for 1000w models, and
120 Vac, 20amp dedicated circuit for 1440w models. Provide strain relief for all wiring.
A. Black/hot wire to “L1” terminal (See Fig.2).
B. White/neutral wire to “NEUT ” terminal (See Fig.2).
C. Green or ground wire to green housing ground screw.
CORD CONNECTED MODELS
For cord connected models, plug the unit into a nema type 5-15R receptacle on a dedicated 15amp or 20 amp circuit
depending on model.
FAN
L1
FAN
N
NEUTL
L1
STAGE 2
FIELD NEUTRAL
WIRE
FIELD LINE
IN
FIELD
GROUND
(GREEN CHASSIS SCREW)
FIELD
WIRING
DIAGRAM
USE
COPPER
CONDUCTORS
ONLY
HEATER
L1
STAGE 1
Fig. 1
Fig. 2