ECO 1-7639 60220 REV.- FORM: 8224
3 of 4
CONTROL WIRING
The HotPod
is provided with a low voltage wall thermostat
.
1. Disconnect the power supply to the HotPod.
2.
For the HotPod Control Board connection remove approximately 2 1/2” of the the outer jacket from the thermostat
cable,
20 AWG min. solid conductor is recommended. Use electrical materials approved by applicable codes.
3. Feed thermostat cable through the “double d” hole in control board enclosure.
4. Connect the wires to the proper terminals. (See Fig.3)
5.
Place strain relief (provided) around the thermostat cable, approximately 3 1/2 inches from stripped end. Using
a pair of pliers press firmly onto cable and into “double d” shaped hole provided in control board enclosure.
THERMOSTAT INSTALLATION
FOR ‘HARD-WIRED’ THERMOSTATS
Note: All thermostats may not operate the HotPod correctly. The thermostat must operate the fan with the heat.
Fig. 3
R W W2 Y/G C
2.5"
RED - 'R' HOT WIRE
WHITE - 'W1' HEAT
GREEN - 'Y/G' FAN
BLUE - 'C' COMMON
JUMPER - FACTORY INSTALLED
'W1 AND 'W2' TERMINALS
HOTPOD CONNECTIONS
HOTPOD CONTROL BOARD
JUMPER
RED
WHITE
BLUE
GREEN
AUXLIM
IT
LIMIT
MOUNTED
ON FAN
FAN
L1
FAN
N
NEUTL
L1
STAGE 2
HEATER
L1
STAGE 1
CL
OSED
OPEN
RED - 'RH'
WHITE - 'W'
GREEN - 'G'
BLUE - 'C'
JUMPER - FACTORY INSTALLED
'RH AND 'RC' TERMINALS
THERMOSTAT CONNECTIONS
STRAIN
RELIEF
TO
THERMOSTAT
1
4"