Vent pipe:
Install vent pipe through the wall thimble and attach to flue outlet collar on top of the fireplace.
Secure all joints with screws and seal with approved "High Temp." self-adhesive aluminum
tape provided.
Adjust the venting so that the vent pipe does not protrude beyond the outer wall.
Wall vent terminal:
1) Engage the terminal with the vent pipe and slide terminal into place. Ensure that both
inner and outer pipes are fully engaged and then attach the terminal to the outside wall.
The vent terminal must not be recessed into the exterior wall or siding.
2) Caulk in place to prevent any moisture entering the building.
NOTE: MINIMUM CLEARANCES TO THE VENT TERMINAL MUST BE MAINTAINED
(see Fig. #
33 & 34
).
Fig. #27
HORIZONTAL
TERMINAL
TCVT.9360
14 1/2" FRAMED
OPENING
WALL SHIELD THIMBLE
TCVT.THIMA
ELBOW
TCVT.811XLB90
MINIMUM 48" VENT
PIPE (TCVT.811X48)
BEFORE THE FIRST
ELBOW.
12" VENT PIPE
TCVT.811X12
* Minimum height from the floor to center of the 14 1/2”
framed opening. The height will need to be increaed
with longer horizontal pipe.
*
84 1/2"
19
TCWS.38CE3 250313-44