background image

 

091009-12 

 

 

 

 

 

TCVT.WSPVB1 

 

 

 

      

                           5  

 

 

 

 

Vertical (Through Roof) Venting

This kit uses either Simpson Duravent GS direct vent pipe, Secure Vent direct vent pipe or Selkirk Direct-
temp vent pipe with a 5” inner pipe and an 8” outer pipe. For part numbers see the table of venting 
components on page 11 of this manual.

Vertical installations must use the optional TCVT.PVVCA vertical adaptor box in conjunction with this kit.

 The vertical 

adaptor box can only be installed on a flat surface. Sloped surfaces require the construction of a chase which provides the 
minimum interior, square opening of 11” x 11” for the venting and wiring to pass through. Flat roofs may require a chase 
depending on local codes and roof construction. (If in doubt check with local inspector)
The terminal must be located in accordance with the clearances outlined in Fig. #1 and 2. 

All part numbers in the following section are shown in Fig. 
#5. 

1. Place the flashing (Part A) onto the chase and seal 
using silicone.

2. Put a bead of silicone on the underside of the vertical 
standoff (Part B) and place it on top of the flashing. Align 
the eight holes and secure both parts to the chase using 
eight #8 x 1 1/2” screws provided.

3. Install the drip shield (Part C) onto the top of the vertical 
standoff using a bead of silicone between the two. Do not 
screw this part in place.

4. Bring the 14-2 electrical wire (not supplied) up through 
the holes in both the flashing and the drip shield leaving at 
least 12” of excess wire above the drip shield.

5. IMPORTANT: Attach an appropriate length(s) of the 
vent to the power vent terminal, sufficient to pass through 
the chase. 

NOTE: DO NOT CONNECT AN ADJUSTABLE LENGTH 
VENT PIPE TO THE TERMINAL.

6. Seal the connection of the first length of pipe at the 
terminal and any other pipe to pipe joint by both screwing 
and taping the outside joint using high temperature foil 
tape.

7. Remove the junction box cover. (Part D)

8. Remove and discard the exhaust shield. (Part E)

9. Apply a bead of silicone on the bottom flange of the 
power vent terminal (TCVT.WSPVB1)

10. Slide the vent through the drip shield and at the same 
time thread the electrical lead through the hole in the 
bottom of the terminal.

11. With the power vent terminal resting on the drip shield, 
align the eight holes in each of the vertical standoff, the 
drip shield and the power vent terminal and then screw 
them together using the eight #8 x 1/2” stainless screws 
provided.

12. Join the 14-2 wire lead to the blower wires using 
the appropriate connectors and attach the ground wire. 
Reinstall the junction box cover.

13. Install the vertical rain cap (Part F) over the power vent 
blower. ALIGN THE EXHAUST OUTLET ON THE POWER 
VENT TERMINAL WITH THE EXHAUST PORT ON THE 
VERTICAL RAIN CAP. 

14. Secure the vertical rain cap to the power vent blower 
with the remaining eight #8 x 1/2” stainless screws. 

NOTE:
THERE ARE NO PILOT HOES IN THE BASE OF THE 
POWER VENT TERMINAL. 1/8” DIAMETER PILOT 
HOLES SHOULD BE DRILLED USING THE HOLES IN 
THE VERTICAL RAIN CAP AS A GUIDE.

DO NOT SILICONE THE VERTICAL RAIN CAP TO 
THE POWER VENT TERMINAL AS IT NEEDS TO BE 
REMOVABLE FOR SERVICING.

15. Attach the vent adaptor directly to the appliance with 
three screws provided. (Fig. #4)

16. Connect the high temperature silicone tube to the 
pressure tap on the adaptor, secure with the hose clamp 
provided and route the tube through any hole back to 
control box. (Fig. #4) Tube may touch unit and be trimmed 
if required. 

Note: Ensure that there are no blockages in 

this tube, as this will cause the control to malfunction.

17. Run the required Simpson Duravent GS / Secure Vent 
/ Selkirk Direct-temp pipe from the adaptor to the terminal 
assembly. Assemble as per the vent pipe manufacturer’s 
instructions.

Installation: 

CAUTION: The vent restrictor must be fully 
open for proper operation.

Содержание TCVT.WSPVB1

Страница 1: ... INSTRUCTIONS ARE TO REMAIN WITH THE APPLIANCE INSTRUCTIONS These instructions are supplementary to the Installation and Operating Instructions supplied with the fireplace and should be kept together Refer to the Installation and Operating Instructions for proper gas supply safety requirements and operating instructions Power Vent Terminal TCVT 502461 Vent Adaptor 5096 814 Simpson Duravent 1247 wa...

Страница 2: ...n conjunction with the Town and Country WS fireplaces This installation must conform with local codes or in the absence of local codes with the Natural Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149 1 This appliance must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 7...

Страница 3: ...he regula tor I clearance to service regulator vent outlet 6 feet 1 8 m minimum J clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 12 inches 30 cm minimum K clearance to a mechanical air supply inlet 6 feet 1 8 m minimum L clearance above paved side walk or a paved driveway located on public property 7 feet 2 1 m minimum M clearance under v...

Страница 4: ...r siding 5 Attach the vent adaptor directly to the appliance with three screws Note The inner pipe does not need to be sealed Fig 4 6 Connect the high temperature silicone tube to the pressure tap on the adaptor secure with the hose clamp provided and route the tube through any hole back to control box Fig 4 Tube may touch unit and be trimmed if required Note Ensure that there are no blockages in ...

Страница 5: ...wing and taping the outside joint using high temperature foil tape 7 Remove the junction box cover Part D 8 Remove and discard the exhaust shield Part E 9 Apply a bead of silicone on the bottom flange of the power vent terminal TCVT WSPVB1 10 Slide the vent through the drip shield and at the same time thread the electrical lead through the hole in the bottom of the terminal 11 With the power vent ...

Страница 6: ... 8074 Part C Drip Shield Part B Vertical Standoff Part A Flashing Site Fabricated Chase MUST ALIGN 8 x 1 2 S S 16 Required 8 x 1 1 2 S S 8 REQUIRED NOTE Holes to secure rain cap are not predrilled SILICONE ALL CONNECTING FACES 14 2 Wire w Ground Final Installation Height 21 6 TCVT WSPVB1 091009 12 Fig 5 Vertical Through Roof Venting ...

Страница 7: ...firebox panel if already installed 2 Remove access panel using care not to damage gasket Fig 10 3 Locate and disconnect the spade connectors in the black wire loop on the right side of the module and in the orange wire running from the module to the socket on the valve labelled pilot Fig 11 and 12 4 Using the wires provided connect the 120V hot supply wire to one of the black wires from the contro...

Страница 8: ...etweenthecontrol box and firebox it can still be easily retrieved with the wires 7 Secure the pressure switch to the control box using the 2 screws provided with this kit Fig 15A WARNING Thisswitchmustbeinstalled inaverticalpositionandwillnotfunction if installed otherwise Fig 15B Fig 14 PRESSURE SWITCH ORANGE WIRE Fig 15 Fig 15A LOW SIDE OF SWITCH Fig 15B 8 Continuewithinstallationandreassemble a...

Страница 9: ...k 120 Volt Common wire White 1 4 Male Connector 1 4 Male Connector 1 4 Male Connector 1 4 Male Connector 1 4 Female Connector 1 4 Female Connector 1 4 Female Connector 1 4 Female Connector Wiring the Power Vent Kit provided by Town Country Communication wires Main Pilot Low pressure side egnarO egnarO Pressure switch wire Supplied Power Vent switch wire Supplied kcalB kcalB STANDARD AWG 14 2 WIRE ...

Страница 10: ...8 FLAT WASHER 6 27 OUTLET AIR CHANNEL 1 9 SP100 25 x 75 AK 4 28 DRIP SHIELD 1 10 SCREW 8 32 x1 1 4 RND HD 4 11 8 32 x5 16 PAN QUADREX 1 30 VENT COLLAR 1 12 HEX NUT STAINLESS 18 8 PLAIN 4 31 VENT EXHAUST ASSEMBLY 1 13 1 4 20 x1 2 NC GR 5 HEX C S PLTD 5 32 VERTICAL RAIN CAP TCVT 1 14 5096 814 VENTING ADAPTER 1 33 VERTICAL STANDOFF 1 15 1 4 LDF PAPER 1 34 BLOWER WIRING 1 16 35 TCVT 50271C2 PRESSURE S...

Страница 11: ...lbow 1605424B Cathedral ceiling support box blk 1605500 Firestop spacer 1605460B Wall thimble blk 1605430 Wall support band SIMPSON DURAVENT COMPONENTS Number Description 1208 6 Pipe Length 1207 9 Pipe Length 1206 12 Pipe Length 1204 24 Pipe Length 1203 36 Pipe Length 1202 48 Pipe Length 1211 11 to 14 5 8 Pipe Adjustable 1217 4 10 Pipe Adjustable 1245 45 Elbow 1290 90 Elbow 1240 Round Ceiling Supp...

Страница 12: ...TECHNICAL SUPPORT 1 250 748 1184 www townandcountryfireplaces net 2975 Allenby Rd Duncan BC V9L 6V8 Printed in Canada ...

Отзывы: