VENTING CONFIGURATIONS

Maximum vent length is 110 ft
plus six 90-degree elbows or 
combination of other elbows 
equaling 90-degrees, with a 
maximum 66 foot vertical rise.
Minimum vent length is 4 ft 
plus one 90-degree elbow. 
The vent can be installed 
with any combination of rise 
and run between the figures 
including up to 3 ft below 
the unit. Ensure vent pipe is 
properly supported. 

Maximum combined 
vertical & horizontal 
venting -
110 ft plus six 
90-degree elbows. 

Vertical Application must use TCVT.PVVCA Box in 

conjunction with this kit

4 ft min. 

6 ft min. 

Maximum 
vertical of 66 ft

Min. venting - 4 ft plus
one 90-degree elbow

3 ft below unit (Max) to
centerline of vent pipe

Fig. #1

 

    
Max Pipe 
Length

 

 2      

 

 

 

 

 

  TCVT.WSPVB1      

 

 

 

                         091009-12 

 

 

 

 

 

Contents of Power Vent Kit

   

 

 

Power Vent Installation 

Locate the fireplace as per the main instructions supplied.
Make the following modifications to add the components used with the Power Vent Kits. This Kit can only be used in 
conjunction with the Town and Country WS fireplaces. This installation must conform with local codes or, in the absence 
of local codes, with the Natural Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, 
CSA B149.1. This appliance must be electrically grounded in accordance with local codes or, in the absence of local 
codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical code, CSA C22.1.

MINIMUM CLEARANCES TO 
COMBUSTIBLE

Vertical vent pipe:
 

 

1.5 in. (38mm)

Horizontal vent pipe:

Top   

1.5 in. (38mm)

Sides 

1.5 in. (38mm)

Bottom 

1.5 in. (38mm)    

All other clearances are as 
per the fireplace installation 
instructions.

Fig. #1a

WALL TERMINATION VENTING CHART

 

 

          49”              0”    110 feet 

4 feet

 

 

          57”            12”    109 feet 

3 feet

 

 

          65”            24”    108 feet 

2 foot

    
Min Pipe 
Length

    A             B                   C

    
Pipe 
Length

    
Min.
Rise

ITEM

PART No.

DESCRIPTION

QTY. ITEM

PART No.

DESCRIPTION

QTY.

1

TCVT.502461

Power Vent Terminal

1

5

5027.15

Pressure Switch

1

2

5096.814

Venting Adaptor

1

6

8240

Tubing, TYSC-516316-100

1

3

TCVT.50271C2

Pressure Switch Wiring

1

7

Hose Clamp

1

4

8271

Pressure Switch Bracket

1

8

5093.02

Hose Clamp

1

9

TCVT.507156C

PV Module Switch Wire

1

Содержание TCVT.WSPVB1

Страница 1: ... INSTRUCTIONS ARE TO REMAIN WITH THE APPLIANCE INSTRUCTIONS These instructions are supplementary to the Installation and Operating Instructions supplied with the fireplace and should be kept together Refer to the Installation and Operating Instructions for proper gas supply safety requirements and operating instructions Power Vent Terminal TCVT 502461 Vent Adaptor 5096 814 Simpson Duravent 1247 wa...

Страница 2: ...n conjunction with the Town and Country WS fireplaces This installation must conform with local codes or in the absence of local codes with the Natural Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149 1 This appliance must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 7...

Страница 3: ...he regula tor I clearance to service regulator vent outlet 6 feet 1 8 m minimum J clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 12 inches 30 cm minimum K clearance to a mechanical air supply inlet 6 feet 1 8 m minimum L clearance above paved side walk or a paved driveway located on public property 7 feet 2 1 m minimum M clearance under v...

Страница 4: ...r siding 5 Attach the vent adaptor directly to the appliance with three screws Note The inner pipe does not need to be sealed Fig 4 6 Connect the high temperature silicone tube to the pressure tap on the adaptor secure with the hose clamp provided and route the tube through any hole back to control box Fig 4 Tube may touch unit and be trimmed if required Note Ensure that there are no blockages in ...

Страница 5: ...wing and taping the outside joint using high temperature foil tape 7 Remove the junction box cover Part D 8 Remove and discard the exhaust shield Part E 9 Apply a bead of silicone on the bottom flange of the power vent terminal TCVT WSPVB1 10 Slide the vent through the drip shield and at the same time thread the electrical lead through the hole in the bottom of the terminal 11 With the power vent ...

Страница 6: ... 8074 Part C Drip Shield Part B Vertical Standoff Part A Flashing Site Fabricated Chase MUST ALIGN 8 x 1 2 S S 16 Required 8 x 1 1 2 S S 8 REQUIRED NOTE Holes to secure rain cap are not predrilled SILICONE ALL CONNECTING FACES 14 2 Wire w Ground Final Installation Height 21 6 TCVT WSPVB1 091009 12 Fig 5 Vertical Through Roof Venting ...

Страница 7: ...firebox panel if already installed 2 Remove access panel using care not to damage gasket Fig 10 3 Locate and disconnect the spade connectors in the black wire loop on the right side of the module and in the orange wire running from the module to the socket on the valve labelled pilot Fig 11 and 12 4 Using the wires provided connect the 120V hot supply wire to one of the black wires from the contro...

Страница 8: ...etweenthecontrol box and firebox it can still be easily retrieved with the wires 7 Secure the pressure switch to the control box using the 2 screws provided with this kit Fig 15A WARNING Thisswitchmustbeinstalled inaverticalpositionandwillnotfunction if installed otherwise Fig 15B Fig 14 PRESSURE SWITCH ORANGE WIRE Fig 15 Fig 15A LOW SIDE OF SWITCH Fig 15B 8 Continuewithinstallationandreassemble a...

Страница 9: ...k 120 Volt Common wire White 1 4 Male Connector 1 4 Male Connector 1 4 Male Connector 1 4 Male Connector 1 4 Female Connector 1 4 Female Connector 1 4 Female Connector 1 4 Female Connector Wiring the Power Vent Kit provided by Town Country Communication wires Main Pilot Low pressure side egnarO egnarO Pressure switch wire Supplied Power Vent switch wire Supplied kcalB kcalB STANDARD AWG 14 2 WIRE ...

Страница 10: ...8 FLAT WASHER 6 27 OUTLET AIR CHANNEL 1 9 SP100 25 x 75 AK 4 28 DRIP SHIELD 1 10 SCREW 8 32 x1 1 4 RND HD 4 11 8 32 x5 16 PAN QUADREX 1 30 VENT COLLAR 1 12 HEX NUT STAINLESS 18 8 PLAIN 4 31 VENT EXHAUST ASSEMBLY 1 13 1 4 20 x1 2 NC GR 5 HEX C S PLTD 5 32 VERTICAL RAIN CAP TCVT 1 14 5096 814 VENTING ADAPTER 1 33 VERTICAL STANDOFF 1 15 1 4 LDF PAPER 1 34 BLOWER WIRING 1 16 35 TCVT 50271C2 PRESSURE S...

Страница 11: ...lbow 1605424B Cathedral ceiling support box blk 1605500 Firestop spacer 1605460B Wall thimble blk 1605430 Wall support band SIMPSON DURAVENT COMPONENTS Number Description 1208 6 Pipe Length 1207 9 Pipe Length 1206 12 Pipe Length 1204 24 Pipe Length 1203 36 Pipe Length 1202 48 Pipe Length 1211 11 to 14 5 8 Pipe Adjustable 1217 4 10 Pipe Adjustable 1245 45 Elbow 1290 90 Elbow 1240 Round Ceiling Supp...

Страница 12: ...TECHNICAL SUPPORT 1 250 748 1184 www townandcountryfireplaces net 2975 Allenby Rd Duncan BC V9L 6V8 Printed in Canada ...

Отзывы: