- 20 - 

tousek

  /  EN_ST-80A_04  /  25. 03. 2020

 

Tousek boom lamp kit

•  The barrier can be equipped with a boom lamp kit 

24Vd.c.,max. 5W,

 consisting of 6 lamps. 

• 

Note:

 The kit for round booms (Product No. 13710250) must be connected via a specially dimensioned series resistor 

(R boom lamp)

 to the control board ST 80A 

(see figure),

 the kit for flat booms (Art.Nr. 13710190) 

without a resistor.

 

Connection of boom lamp kit 

• 

ATTENTION: turn off power supply!

      

•  When using the kit for round booms (Prod. No. 13710250) 

slide the connecting cable of the boom lights into the ope

-

ning of the protective resistor and fix it with Crimp wrench.

•  Connect to 

terminals 70/71

 of the control ST 80A.

70

71

74

75

9/1

9/2

9/3

9/4

78

79

boom lamp

fix

 

Signal lamp

•  A signal lamp 

230V, max. 100W

 

can be connected at 

  terminals 10/11.

10

11

ST 80(V)A

Light / Lamps 

Connections and adjustments ST 80(V)A

 Warning

 

 • 

Before connection works please turn off the main power switch !

  

• 

Safety rules please see page 11 !

 

Prewarning OPEN  

(signal lamp: terminals 10/11)

 

Light / Lamps

 

turned off

 

1–30s adjustable:

 

Before each opening movement the 

signal lamp/ flashing light is activated for the adjusted 

time.

 

Boom lamp CLOSE  

(terminals 70 (-) / 71 (+))

 

Light / Lamps

•  The boom lamp blinks during movement and stops blinking in open position.
•  For the prewarning time the adjustments for the signal lamp are valid
•  For closed position you can choose one of the following functions:

 

OFF

 

blinks:

 boom lamp blinks in closed position

 

illuminates:

 boom lamp  illuminates in closed position

   

Green phase  

 20s (factory setting)    

 

Light / Lamps

 

5–120s adjustable [in 1 steps]:

 duration of green phase.

   

Clearance time 

 5s (factory setting)      

Light / Lamps

 

1–60s adjustable [in 1 steps]:

 time to leave the traffic light intermediate area.

   

Traffic light gate CLOSED

      

Light / Lamps

 

OFF: 

red traffic light does not illuminate in closed position.

 

Constant red:

 red traffic light illuminates also in closed position. 

   

Traffic light logic

      

Light / Lamps

 

both sides green: 

both traffic lights illuminate in open position GREEN, regardless of which side has been given the 

green request.

 

one side green :

 

 

only the traffic light illuminates in open position GREEN, from the side from where the green request 

has been requested.

Содержание ST 80A

Страница 1: ...Installation and connection manual Barrier control unit ST 80A ST 80VA in combination with traffic light control STA 11...

Страница 2: ...terminals 45 46 16 Photocells connection examples 16 17 G Main closing edge terminals 50 52 18 PHC ISD function 18 PHC ISD pause time 18 PHC test 18 Motor 19 max force 19 ARS response time 19 Speed OP...

Страница 3: ...on and operating instructions The TOUSEK Ges m b H rejects any liability if the product is used in any way not fully conforming to its original purpose as stated herein Children have to be instructed...

Страница 4: ...l radio receivers and induction loop detector Operator control board ST 80 V A Traffic light control board STA 11 General For the implementation of the traffic light system the traffic light control b...

Страница 5: ...ED 2 opening command INSIDE or OUTSIDE RED RED Prewarning OPEN is being started red traffic light warning and possibly signal light warning before opening the door gate duration adjustable via gate au...

Страница 6: ...mand FE Slot for optional radio receiver p 8 F fuse 3 15A T Warning Before opening the control board box please switch off necessarily the main switch In supplied control inside the unit is powered th...

Страница 7: ...rator control board see operator control board 97 6 99 6 96 6 98 6 GREEN outside RED outside GREEN inside RED inside Traffic light outputs outside GREEN term 97 6 RED term 99 6 inside GREEN term 96 6...

Страница 8: ...raffic light control board STA 11 Important With the use of the 2 channel receiver the first chan nel takes over the function for the impulse switch outside and the second channel the function for the...

Страница 9: ...tousek EN_ST 80A_04 25 03 2020 9...

Страница 10: ...op fu Without function in connection with traffic light control board ZM Slot for optional module Status display p 24 T Transformer F1 safety fuse F 5A F2 safety fuse F 2A 3 Barrier control board ST 8...

Страница 11: ...e turned off If the control is power supplied its inner part is under tension In order to avoid electrical strokes the safety regulations have to be respected The device may only be connected by train...

Страница 12: ...value of a parameter is given When pressing the button you return to the superior menu point Possibly changed adjustments of a parameter are rejected with this button the former values will remain AU...

Страница 13: ...g only with ST 80VA active not active lights lamps see page 20 prewarning OPEN OFF 1 30s OFF Green phase 5 120s increment 1 20s Clearance time 1 60s increment 1 5s Traffic light gate CLOSED OFF consta...

Страница 14: ...o be kept The device may only be connected by trained profes sionals Theproductisnotsuitableforinstallationinexplosion hazardous areas Anall poledisconnectingmainsswitchwithacontact opening gap of min...

Страница 15: ...unction of I loops has to be selected under ISD channel 1 and ISD channel 2 I loops can be connected onto the traffic light control board STA 11 as command transmitters For this the STA 11 has also to...

Страница 16: ...uencies Photocell self test function The control board is equipped with a self test function for the connected photocell With an opening impulse switch or button the transmitter of the photocell is sw...

Страница 17: ...upport SYNC function the photocell transmitters and receivers have to be mounted on different sides 2 Photocells Tousek LS 45 2 as safety device Photocells Tousek RLS 620 as safety device 24Va c 12 24...

Страница 18: ...uption of the photocell induction loop during closing makes the barrier reverse open In automatic mode the barrier closes as soon as the pause time has run out In impulse operation another closing com...

Страница 19: ...able increment 5 determines the max possible motor force ARS response time 0 5s factory setting Motor 0 15 0 95s closing speed adjustable increment 0 05 determines in which time the AR System responds...

Страница 20: ...0 11 Light Lamps turned off 1 30s adjustable Before each opening movement the signal lamp flashing light is activated for the adjusted time Boom lamp CLOSE terminals 70 71 Light Lamps The boom lamp bl...

Страница 21: ...y of the optional module in control unit ST 80 V A p 24 Max contact load 1A 24Va c d c Signal contacts Description status display module see page 24 Peripherals Status display 1 with the two potential...

Страница 22: ...ES reset back to factory settings and delete the adjusted limits The end posistions limits will be redetermined after impulse Software version control function Reset Diagnosis shows the software versi...

Страница 23: ...perator control board ST 80 V A the I loop function depends on the settings under buttons switches ISD channel 1 2 safety PHC ISD function and safety PHC ISD pause time Detailed informations can be fo...

Страница 24: ...under Peripherals Signal contacts p 21 Connection the module Turn off the power supply Plug in the status display module into the slot ZM With the potential free signal contacts K1 term 90 91 and K2 t...

Страница 25: ...ell active Main safety edge active Photocell not active Main safety edge not active change YES confirm change YES confirm BASIC SETTINGS For setting the most important adjustments for initial operatio...

Страница 26: ...bstacle or is too hard to move check adjustment of forces remove obstacle hence check if boom is easy to move Display photocell test negative interruption or hot wired photocell check correct connecti...

Страница 27: ...ek EN_ST 80A_04 25 03 2020 27 Dimensions in mm We reserve the right to change dimensions and technical specifications without prior notice 240 195 Depth 105 8 Dimensioned drawing of housing IP54 ST 80...

Страница 28: ...Gliwicka 67 Tel 48 32 738 53 65 Fax 48 32 738 53 66 info tousek pl Tousek s r o Czech Republic CZ 252 61 Jene u Prahy Pr myslov 499 Tel 420 777 751 730 info tousek cz We reserve the right to change d...

Отзывы: