Attention
Please check the adjustments to be in compliance with the valid safety regulations and standards that have to
be strictly followed !
Operating logic
Connections and adjustments ST 80(V)A
Impulse logic
Operating logic
without pause time extension:
a command in automatic mode during pause time does not lead to a pause time
extension. The impulse is being ignored.
Forced closing (only with ST 80VA)
Operating logic
active:
this function causes that a manually released boom goes immediately back to closure.
not active:
the forced closing is deactivated
Motor
Connections and adjustments ST 80(V)A
max. force
100% (factory setting)
Motor
50–100% adjustable [increment 5]:
determines the max. possible motor force.
ARS response time
0,5s (factory setting)
Motor
0,15–0,95s closing speed adjustable [increment 0,05]:
determines, in which time the AR-System responds. The
lower the value, the more sensitive the sensor will react.
Speed OPEN
90% for ST80A /
100% for ST80VA (factory setting)
Motor
55–100% adjustable [increment 5]:
determines the speed of motor during opening.
At barriers with 6m boom length the setting for speed OPEN must not be more than 90% (= factory
setting of ST 80A)
!
Speed CLOSE
90% for ST80A /
100% for ST80VA (factory setting)
Motor
55–100% adjustable [increment 5]:
determines the speed of motor during closing.
At barriers with 6m boom length the setting for speed CLOSE must not be more than 90% (= factory
setting of ST 80A)
!
Soft runtime
1,5s for ST80A /
1s for ST80VA (factory setting)
Motor
0–5s adjustable [increment 0,1]:
determines the time of softstop.