TOTALINE TOTALINE P707 Скачать руководство пользователя страница 6

6

Direct Connection of Supply Airstream and Exhaust Air-
Stream to the Furnace Cold Air Return (Return/Return
Method) — The HRV must be balanced. It is mandatory that
the furnace blower run continuously or HRV operation be in-
terlocked with the furnace blower. Check local codes/authority
having jurisdiction for acceptance. See Fig. 17 and 18.
Direct Connection of Both Supply Airstream and Exhaust
Airstream to the Furnace Cold Air Return and Supply Air
Side (Supply/Return Method) — The HRV must be balanced.
It is recommended that the furnace blower run continuously or
HRV operation be interlocked with the furnace blower. Check
local codes /authority having jurisdiction for acceptance. See
Fig. 19 and 20.

Step 7 — Airflow Balancing —

If the unit airflows

are not properly balanced then the unit may not operate at max-
imum efficiency and energy recovery core damage may occur.

An improperly balanced unit could cause negative or

positive pressure in the home causing cold air to enter or other
combustible equipment to backdraft. Also, the unit may not
defrost properly.

The balancing procedure consists of measuring the exhaust

air leaving the system and the supply air entering the system
and ensuring that these two are equal. A deviation of 10% or
less is acceptable. In such cases, it is recommended to have a
greater amount of exhaust air than supply which will increase
the supply-air temperature.
AIRFLOW STATION METHOD — To measure airflow with
an airflow station, perform the following:

1. Cut the duct and insert the flow measuring station.

Make sure that the flow measuring station air direction
arrow points in the direction of the airflow. Secure the
flow measuring station with duct tape. See Fig. 21.

2. Before taking the reading, make sure that the Magne-

helic gage is level and at 0. See Fig. 22.

3. Start the HRV and other system devices if applicable

(furnace and air handler) and refer to the flow measur-
ing station chart to determine unit airflow velocity.

4. The airflow is regulated by a balancing damper located

inside the collar of the HRV. Adjust the Supply Air Out
damper until the desired velocity is achieved. See Fig. 23.

5. Adjust the Exhaust Air Out damper in the same

manner.

Fig. 17 — Direct Connection to Furnace

(Return/Return)

FORCED AIR

FURNACE

COOL AIR

RETURN

RETURN AIR

1 M

(3'-3") MIN

RECOMMENDED

* UNIT IS NORMALLY BALANCED ON HIGH SPEED 

WITH FURNACE BLOWER ON.

OUTDOORS

* DUCTS CONNECTION MAY VARY

DEPENDING ON MODEL

EXHAUST AIR FROM VARIOUS

PARTS OF HOME.

I.E., BATHROOMS (IF REQUIRED)

KITCHENS (IF REQUIRED)

NOTES:

1. Furnace blower may be required to operate when HRV is on to provide good air distribution.
2. Weather hood arrangement is for drawing purposes only. 6

 (2 m) minimum separation recommended. 18

 (460 mm) above grade minimum.

3. Due to the differences in pressure between the HRV and the equipment it is being connected to, the HRV’s airflow must be confirmed on site,

using the balancing procedure found in the installation manual.

Fig. 16 — Partially Dedicated System Airflow Diagram

Содержание TOTALINE P707

Страница 1: ...ompo nents and equipment location roofs elevated structures etc Only trained qualified installers and service mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes GENERAL The P707 SHR1504 and P707 SHR2004 Heat Recovery Ventilators HRV are use...

Страница 2: ...e There should be access to a water drain for condensate removal of the unit during defrost The unit should be located in a heated area attic installation is not recommended The location should also minimize any noise level that would be created by the unit in the living area Make sure there is adequate access for future maintenance Step 2 Unit Mounting The unit is typically hung from the ceiling ...

Страница 3: ...ld be slightly larger than the collar to allow for the thickness of the insulated flexible duct See Fig 8 2 Cut a holes using the outline from Step 1 See Fig 8 When cutting or drilling holes be careful not to dam age electrical wiring or other hidden objects in wall 3 Pull the insulated flexible duct through the opening until it is well extended and straight Slide the duct inner vinyl sleeve over ...

Страница 4: ...rically low voltage with the HRV accessory control contacts for intermittent demand To hard duct the supply air directly into the cold air return of the furnace remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10 Make sure that the minimum distance from the supply air of the HRV to the furnace is followe...

Страница 5: ...n Stale air is drawn from key areas of home bathroom kitchen laundry Fresh air is supplied to main living areas The HRV must be balanced See Fig 14 Partially Dedicated System Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas via the forced air system HRV must be bal anced See Fig 15 and 16 SUPPLY EXHAUST BEDROOMS FRESH AIR EXHAUST AIR 1800 MM 4...

Страница 6: ...re AIRFLOW STATION METHOD To measure airflow with an airflow station perform the following 1 Cut the duct and insert the flow measuring station Make sure that the flow measuring station air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape See Fig 21 2 Before taking the reading make sure that the Magne helic gage is level and at 0 See Fig 22 3 ...

Страница 7: ...s the highest airflow highest reading on the gage 6 Use the HRV dampers to correct the airflow to match the lower reading from the other duct The flows should now be balanced 7 Actual airflow can be determined from the gage reading The value read on the gage is called the veloc ity pressure The pitot tube comes with a chart that will give the airflow velocity based on the velocity pressure indicat...

Страница 8: ...d installation in the fresh air to building duct Install the damper and adjust as necessary DUCT DIAMETER in AREA sq ft 5 0 14 6 0 20 7 0 27 8 0 35 FORCED AIR FURNACE COOL AIR RETURN RETURN AIR 1 M 3 3 MIN RECOMMENDED UNIT IS NORMALLY BALANCED ON HIGH SPEED WITH FURNACE BLOWER ON OUTDOORS DUCTS CONNECTION MAY VARY DEPENDING ON MODEL 1 M 3 3 MIN RECOMMENDED NOTES 1 Furnace blower may be required to...

Страница 9: ...stem For these thermostats use the alternate control contacts wiring See Fig 27 Magnehelic Magnehelic OUTDOORS PLACE PITOT TUBE A MINIMUM OF 18 FROM BLOWER OR ELBOWS NOTE DUCT CONNECTIONS MAY VARY DEPENDING ON MODEL MAGNEHELIC GAGE PITOT TUBE PITOT TUBE MAGNEHELIC GAGE Pitot tube should be kept at least 12 in away from fans elbows and dampers to ensure accurate reading Fig 24 Pitot Tube Balancing ...

Страница 10: ...ering set the dehumidistat at its highest level and the switch on the HRV to standby If the Intellitek series controller is installed the air exchanger can be stopped at any time by turning the HRV off from the wall control However continuous ventilation is recommended Fall Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on...

Страница 11: ...ated for life They require no maintenance Chassis The inside of the unit should be vacuumed yearly Be careful not to damage any of the mechanical compo nents and electrical connections Condensation Panel The condensation panel should be cleaned yearly Drain and Drain Line Units with drain lines should have their line and connection checked regularly Outside Hoods The outside hoods need to be check...

Страница 12: ... clean core House grilles closed or blocked Check and open grilles Dampers are closed if installed Check and open dampers Poor power supply at site Have electrician check supply voltage at house Ductwork is restricting HRV operation Check duct installation Improper speed control setting Increase the speed of the HRV HRV airflow improperly balanced Have contractor balance HRV Supply Air Feels Cold ...

Страница 13: ...BLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or inter...

Страница 14: ......

Страница 15: ......

Страница 16: ...inue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P707 5SI CARRIER CORPORATION 2004 4 04 REPLACES New PRINTED IN U S A CATALOG NUMBER 570 332 ...

Отзывы: