background image

11

CONTINUOUS/VENTILATION MODE — In this mode of
operation, both fans are operating and exchanging air with the
outside. The heat recovery ventilator constantly exchanges the
air at the selected rate, either at low or medium speed, and
switches to high speed when activated by an accessory remote
control. The low and medium fan speed selection will cause the
unit to operate in continuous exchange mode at an exchange
rate of 35% and 50% maximum airflow rating respectively.
Continuous mode is recommended, since pollutants are slowly
but constantly being generated in the house. See Fig. 28.
INTERMITTENT/STANDBY MODE — The system is al-
ways on standby and operates at high speed when activated by
an accessory remote control. Standby should be selected if the
user wishes to stop the unit from continuous exchange. It is rec-
ommended that the Standby mode only be used if the system is
equipped with an accessory external control, in which case, the
unit would activate to High fan speed, until the control is satis-
fied and then return to standby (off). See Fig. 29.
DEFROST (FAN SHUTDOWN) — The automatic defrost
cycle consists of a fan shutdown. When the supply airstream
temperature goes below 23 F, the supply motor shuts down and
the exhaust motor goes in to high speed. Ambient air is passed
through the unit for a period of 5 minutes. The supply motor
will then restart and run at the preset speed. The exhaust motor
will also slow down to the preset speed, and the unit will oper-
ate in the run cycle for 25 minutes. This fan shutdown defrost
cycle continues until the supply airstream rises above 32 F. See
Fig. 30.

MAINTENANCE

A yearly inspection is recommended to ensure the efficien-

cy and trouble-free use of the HRV. Verify the different operat-
ing modes.

Motor —

The motors are factory balanced and lubricated for

life. They require no maintenance.

Chassis —

The inside of the unit should be vacuumed

yearly. Be careful not to damage any of the mechanical compo-
nents and electrical connections.

Condensation Panel —

The condensation panel should

be cleaned yearly.

Drain and Drain Line —

Units with drain lines should

have their line and connection checked regularly.

Outside Hoods —

The outside hoods need to be checked

every season to make sure there are no debris, leaves, or insects
blocking the airflow. Check regularly that there are no pollut-
ants near the intake hood. Make sure the hoods are clear of any
snow accumulation during the winter months.

Filters —

The filters need to be checked and cleaned every

three months or when they appear dirty. This unit has two
filters.

To clean, remove the filters and vacuum. If the filters still

appear dirty, they can be washed in warm water and mild
detergent. Replace the filters if they become too soft after
washing. The filters should be replaced yearly or when they
can no longer be cleaned properly. The metal electrostatic filter
may need to be changed after washing a few times.

Heat Recovery Core —

Clean

the

heat

recovery

polypropylene core annually or as needed with a vacuum
cleaner. Use a soft brush attachment. If the core still appears
dirty, it can be washed with warm water and mild detergent.
Make sure the filters on the unit are cleaned. Failure to clean or
use filters may damage the heat recovery core and void the
warranty.
NOTE: The use of the heat recovery core in adverse envi-
ronment conditions such as dust, oil mist, excessive kitchen
grease, corrosive fumes, organic solvents, paint or any other
harmful chemicals can damage the heat recovery core and
void the warranty.

Make sure HRV is unplugged before performing any main-
tenance. Injury from electric shock could result.

AIR FROM

HOUSE

AIR FROM

 OUTSIDE

AIR TO

HOUSE

AIR TO

 OUTSIDE

* NO EXCHANGE OF AIR

AIR FROM

HOUSE

AIR TO

OUTSIDE

Fig. 28 — Continuous Mode

Fig. 29 — Intermittent Mode

Fig. 30 — Defrost Mode

Содержание TOTALINE P707

Страница 1: ...ompo nents and equipment location roofs elevated structures etc Only trained qualified installers and service mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes GENERAL The P707 SHR1504 and P707 SHR2004 Heat Recovery Ventilators HRV are use...

Страница 2: ...e There should be access to a water drain for condensate removal of the unit during defrost The unit should be located in a heated area attic installation is not recommended The location should also minimize any noise level that would be created by the unit in the living area Make sure there is adequate access for future maintenance Step 2 Unit Mounting The unit is typically hung from the ceiling ...

Страница 3: ...ld be slightly larger than the collar to allow for the thickness of the insulated flexible duct See Fig 8 2 Cut a holes using the outline from Step 1 See Fig 8 When cutting or drilling holes be careful not to dam age electrical wiring or other hidden objects in wall 3 Pull the insulated flexible duct through the opening until it is well extended and straight Slide the duct inner vinyl sleeve over ...

Страница 4: ...rically low voltage with the HRV accessory control contacts for intermittent demand To hard duct the supply air directly into the cold air return of the furnace remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10 Make sure that the minimum distance from the supply air of the HRV to the furnace is followe...

Страница 5: ...n Stale air is drawn from key areas of home bathroom kitchen laundry Fresh air is supplied to main living areas The HRV must be balanced See Fig 14 Partially Dedicated System Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas via the forced air system HRV must be bal anced See Fig 15 and 16 SUPPLY EXHAUST BEDROOMS FRESH AIR EXHAUST AIR 1800 MM 4...

Страница 6: ...re AIRFLOW STATION METHOD To measure airflow with an airflow station perform the following 1 Cut the duct and insert the flow measuring station Make sure that the flow measuring station air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape See Fig 21 2 Before taking the reading make sure that the Magne helic gage is level and at 0 See Fig 22 3 ...

Страница 7: ...s the highest airflow highest reading on the gage 6 Use the HRV dampers to correct the airflow to match the lower reading from the other duct The flows should now be balanced 7 Actual airflow can be determined from the gage reading The value read on the gage is called the veloc ity pressure The pitot tube comes with a chart that will give the airflow velocity based on the velocity pressure indicat...

Страница 8: ...d installation in the fresh air to building duct Install the damper and adjust as necessary DUCT DIAMETER in AREA sq ft 5 0 14 6 0 20 7 0 27 8 0 35 FORCED AIR FURNACE COOL AIR RETURN RETURN AIR 1 M 3 3 MIN RECOMMENDED UNIT IS NORMALLY BALANCED ON HIGH SPEED WITH FURNACE BLOWER ON OUTDOORS DUCTS CONNECTION MAY VARY DEPENDING ON MODEL 1 M 3 3 MIN RECOMMENDED NOTES 1 Furnace blower may be required to...

Страница 9: ...stem For these thermostats use the alternate control contacts wiring See Fig 27 Magnehelic Magnehelic OUTDOORS PLACE PITOT TUBE A MINIMUM OF 18 FROM BLOWER OR ELBOWS NOTE DUCT CONNECTIONS MAY VARY DEPENDING ON MODEL MAGNEHELIC GAGE PITOT TUBE PITOT TUBE MAGNEHELIC GAGE Pitot tube should be kept at least 12 in away from fans elbows and dampers to ensure accurate reading Fig 24 Pitot Tube Balancing ...

Страница 10: ...ering set the dehumidistat at its highest level and the switch on the HRV to standby If the Intellitek series controller is installed the air exchanger can be stopped at any time by turning the HRV off from the wall control However continuous ventilation is recommended Fall Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on...

Страница 11: ...ated for life They require no maintenance Chassis The inside of the unit should be vacuumed yearly Be careful not to damage any of the mechanical compo nents and electrical connections Condensation Panel The condensation panel should be cleaned yearly Drain and Drain Line Units with drain lines should have their line and connection checked regularly Outside Hoods The outside hoods need to be check...

Страница 12: ... clean core House grilles closed or blocked Check and open grilles Dampers are closed if installed Check and open dampers Poor power supply at site Have electrician check supply voltage at house Ductwork is restricting HRV operation Check duct installation Improper speed control setting Increase the speed of the HRV HRV airflow improperly balanced Have contractor balance HRV Supply Air Feels Cold ...

Страница 13: ...BLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or inter...

Страница 14: ......

Страница 15: ......

Страница 16: ...inue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P707 5SI CARRIER CORPORATION 2004 4 04 REPLACES New PRINTED IN U S A CATALOG NUMBER 570 332 ...

Отзывы: