TROUBLESHOOTING

See Table 2 for troubleshooting.

Table 2 — Troubleshooting

                                    LEGEND

PROBLEM

CAUSE

SOLUTION

Air is Too Dry

Dehumidistat control is set too low.

Increase the desired level of humidity. Change 
ventilation mode from continuous mode to 
standby.

HRV out of balance.

Balance HRV.

Air is Too Humid

Dehumidistat control is set too high.

Reduce the desired level of humidity. Use 
continuous exchange mode.

Sudden change in temperature.

Wait until outside temperature stabilizes 
(winter). Heating will also improve humidity of 
air.

Storing too much wood for heating.

Store majority of wood outside. Even dried, a 
cord of wood contains more than 20 gallons of 
water.

Dryer vent exhaust is inside home.

Arrange outside vent for dryer.

Poor air circulation near windows.

Open curtains or blinds. Bay or bow windows 
may require additional air circulation.

HRV out of balance.

Balance HRV.

Basement door is closed.

Open the door or install a grille on the door. 

Air is Too Dry

Dehumidistat control set too low.

Increase the desired level of humidity. Change 
ventilation mode from continuous to standby.

HRV out of balance.

Balance HRV.

Persistent Condensation
on Window

Improper adjustment of dehumidistat control.

Reduce the desired level of humidity. Use con-
tinuous exchange mode.

HRV out of balance.

Balance HRV.

Poor Airflow

1

/

4

-in. mesh on the outside hoods is plugged.

Clean exterior hoods or vents.

Filters plugged.

Remove and clean filter.

Core obstructed.

Remove and clean core.

House grilles closed or blocked.

Check and open grilles.

Dampers are closed if installed.

Check and open dampers.

Poor power supply at site.

Have electrician check supply voltage at 
house.

Ductwork is restricting HRV operation.

Check duct installation.

Improper speed control setting.

Increase the speed of the HRV.

HRV airflow improperly balanced.

Have contractor balance HRV.

Supply Air Feels Cold

Poor location of supply grilles. Airflow may 
irritate the occupant.

Locate the grilles high on the walls or under the 
baseboards. Install ceiling mounted diffuser or 
grilles so as not to directly vent the supply air 
on the occupant.

Turn down the HRV supply speed.

Outdoor temperature extremely cold.

A small duct heater (1 kW) can be used to 
temper the supply air.

Placement of furniture or closed doors is 
restricting the movement of air in the home.
If supply air is ducted into furnace return, the 
furnace fan may need to run continuously to 
distribute ventilation air comfortably.

ERV and/or Ducts Frosting Up

HRV air flows are improperly balanced.

Minimal frost build-up is expected on cores 
before unit initiates defrost cycle functions. 
Balance airflow if needed.

Malfunction of the HRV defrost system.

Have HVAC contractor check the HRV.

Condensation or Ice Build-Up in Insulated Duct 
to the Outside

Incomplete vapor barrier around insulated 
duct.

Tape and seal all joints. Ensure that the vapor 
barrier is completely sealed.

Hole or tear in outer duct covering.

Tape any holes or tears made in the outer duct 
covering. Ensure that the vapor barrier is com-
pletely sealed.

HRV

Heat Recovery Ventilator

HVAC —

Heating, Ventilation and Air Conditioning

Содержание TOTALINE P707

Страница 1: ...ompo nents and equipment location roofs elevated structures etc Only trained qualified installers and service mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes GENERAL The P707 SHR1504 and P707 SHR2004 Heat Recovery Ventilators HRV are use...

Страница 2: ...e There should be access to a water drain for condensate removal of the unit during defrost The unit should be located in a heated area attic installation is not recommended The location should also minimize any noise level that would be created by the unit in the living area Make sure there is adequate access for future maintenance Step 2 Unit Mounting The unit is typically hung from the ceiling ...

Страница 3: ...ld be slightly larger than the collar to allow for the thickness of the insulated flexible duct See Fig 8 2 Cut a holes using the outline from Step 1 See Fig 8 When cutting or drilling holes be careful not to dam age electrical wiring or other hidden objects in wall 3 Pull the insulated flexible duct through the opening until it is well extended and straight Slide the duct inner vinyl sleeve over ...

Страница 4: ...rically low voltage with the HRV accessory control contacts for intermittent demand To hard duct the supply air directly into the cold air return of the furnace remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10 Make sure that the minimum distance from the supply air of the HRV to the furnace is followe...

Страница 5: ...n Stale air is drawn from key areas of home bathroom kitchen laundry Fresh air is supplied to main living areas The HRV must be balanced See Fig 14 Partially Dedicated System Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas via the forced air system HRV must be bal anced See Fig 15 and 16 SUPPLY EXHAUST BEDROOMS FRESH AIR EXHAUST AIR 1800 MM 4...

Страница 6: ...re AIRFLOW STATION METHOD To measure airflow with an airflow station perform the following 1 Cut the duct and insert the flow measuring station Make sure that the flow measuring station air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape See Fig 21 2 Before taking the reading make sure that the Magne helic gage is level and at 0 See Fig 22 3 ...

Страница 7: ...s the highest airflow highest reading on the gage 6 Use the HRV dampers to correct the airflow to match the lower reading from the other duct The flows should now be balanced 7 Actual airflow can be determined from the gage reading The value read on the gage is called the veloc ity pressure The pitot tube comes with a chart that will give the airflow velocity based on the velocity pressure indicat...

Страница 8: ...d installation in the fresh air to building duct Install the damper and adjust as necessary DUCT DIAMETER in AREA sq ft 5 0 14 6 0 20 7 0 27 8 0 35 FORCED AIR FURNACE COOL AIR RETURN RETURN AIR 1 M 3 3 MIN RECOMMENDED UNIT IS NORMALLY BALANCED ON HIGH SPEED WITH FURNACE BLOWER ON OUTDOORS DUCTS CONNECTION MAY VARY DEPENDING ON MODEL 1 M 3 3 MIN RECOMMENDED NOTES 1 Furnace blower may be required to...

Страница 9: ...stem For these thermostats use the alternate control contacts wiring See Fig 27 Magnehelic Magnehelic OUTDOORS PLACE PITOT TUBE A MINIMUM OF 18 FROM BLOWER OR ELBOWS NOTE DUCT CONNECTIONS MAY VARY DEPENDING ON MODEL MAGNEHELIC GAGE PITOT TUBE PITOT TUBE MAGNEHELIC GAGE Pitot tube should be kept at least 12 in away from fans elbows and dampers to ensure accurate reading Fig 24 Pitot Tube Balancing ...

Страница 10: ...ering set the dehumidistat at its highest level and the switch on the HRV to standby If the Intellitek series controller is installed the air exchanger can be stopped at any time by turning the HRV off from the wall control However continuous ventilation is recommended Fall Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on...

Страница 11: ...ated for life They require no maintenance Chassis The inside of the unit should be vacuumed yearly Be careful not to damage any of the mechanical compo nents and electrical connections Condensation Panel The condensation panel should be cleaned yearly Drain and Drain Line Units with drain lines should have their line and connection checked regularly Outside Hoods The outside hoods need to be check...

Страница 12: ... clean core House grilles closed or blocked Check and open grilles Dampers are closed if installed Check and open dampers Poor power supply at site Have electrician check supply voltage at house Ductwork is restricting HRV operation Check duct installation Improper speed control setting Increase the speed of the HRV HRV airflow improperly balanced Have contractor balance HRV Supply Air Feels Cold ...

Страница 13: ...BLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or inter...