2

INSTALLATION

Step 1 — Unit Location —

The HRV must be located

in a heated space where it can be conveniently serviced.
Typically the HRV is located in the mechanical room or an area
close to the outside wall where the weather hoods will be
mounted. If a basement area is not convenient or does not
exist, a utility or laundry room may be used. See Fig. 2 for
dimensions.

Attic installations are not normally recommended due to the

complexity of work to install, freezing conditions in the attic,
and the difficulty of access for service and cleaning.

Connecting appliances to the HRV

is not recommended

(such as a clothes dryer, range top, stovetop fan, or central
vacuum system). These appliances may cause lint, dust or
grease to collect in the HRV, damaging the unit.
NOTE: Connecting any of these type of appliances to the
HRV will invalidate the warranty.

Locate the unit close to the outside wall on which the supply

and exhaust hoods will be mounted. There should be a nearby
power supply of 120 volts, 60 Hz available.

There should be access to a water drain for condensate

removal of the unit during defrost.

The unit should be located in a heated area (attic installation

is not recommended). The location should also minimize any
noise level that would be created by the unit in the living area.

Make sure there is adequate access for future maintenance.

Step 2 — Unit Mounting —

The unit is typically hung

from the ceiling for mounting. See Fig. 2 for unit dimensions.
Perform the following to mount the HRV:

1. Place fastening hooks on the strapping board or the

floor joists. See Fig. 3.

2. Attach a hanging chain (provided) to each no. 10

3

/

4

-in.

bolts (provided) on the top 4 corners of the unit and
tighten. See Fig. 4.

3. Hang the unit by slipping a link onto the hanging

hooks, making sure the unit is level. Unit condensate
will not drain properly unless unit is level. See Fig. 5.

A

B

C

D

E

OUTDOOR 

INTAKE

(FRESH AIR)

EXHAUST

AIR FROM

INSIDE

FRESH AIR

TO INSIDE

EXHAUST

AIR

(TO OUTSIDE)

6"

Fig. 2 — Unit Dimensions

UNIT

A

B

C

D

E

SHR 1504

2

1

/

4

 (56 mm)

23

1

/

2

 (596 mm)

2

5

/

8

 (67 mm)

17

3

/

8

 (441 mm)

16

1

/

8

 (413 mm)

SHR 2004

2

1

/

4

 (56 mm)

27

7

/

8

 (707 mm)

2

5

/

8

 (67 mm)

17

3

/

8

 (441 mm)

20

1

/

2

 (520 mm)

Fig. 3 — Install Fastening Hooks

Fig. 4 — Install Hanging Chain

Fig. 5 — Unit Mounting

Содержание TOTALINE P707

Страница 1: ...ompo nents and equipment location roofs elevated structures etc Only trained qualified installers and service mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes GENERAL The P707 SHR1504 and P707 SHR2004 Heat Recovery Ventilators HRV are use...

Страница 2: ...e There should be access to a water drain for condensate removal of the unit during defrost The unit should be located in a heated area attic installation is not recommended The location should also minimize any noise level that would be created by the unit in the living area Make sure there is adequate access for future maintenance Step 2 Unit Mounting The unit is typically hung from the ceiling ...

Страница 3: ...ld be slightly larger than the collar to allow for the thickness of the insulated flexible duct See Fig 8 2 Cut a holes using the outline from Step 1 See Fig 8 When cutting or drilling holes be careful not to dam age electrical wiring or other hidden objects in wall 3 Pull the insulated flexible duct through the opening until it is well extended and straight Slide the duct inner vinyl sleeve over ...

Страница 4: ...rically low voltage with the HRV accessory control contacts for intermittent demand To hard duct the supply air directly into the cold air return of the furnace remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10 Make sure that the minimum distance from the supply air of the HRV to the furnace is followe...

Страница 5: ...n Stale air is drawn from key areas of home bathroom kitchen laundry Fresh air is supplied to main living areas The HRV must be balanced See Fig 14 Partially Dedicated System Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas via the forced air system HRV must be bal anced See Fig 15 and 16 SUPPLY EXHAUST BEDROOMS FRESH AIR EXHAUST AIR 1800 MM 4...

Страница 6: ...re AIRFLOW STATION METHOD To measure airflow with an airflow station perform the following 1 Cut the duct and insert the flow measuring station Make sure that the flow measuring station air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape See Fig 21 2 Before taking the reading make sure that the Magne helic gage is level and at 0 See Fig 22 3 ...

Страница 7: ...s the highest airflow highest reading on the gage 6 Use the HRV dampers to correct the airflow to match the lower reading from the other duct The flows should now be balanced 7 Actual airflow can be determined from the gage reading The value read on the gage is called the veloc ity pressure The pitot tube comes with a chart that will give the airflow velocity based on the velocity pressure indicat...

Страница 8: ...d installation in the fresh air to building duct Install the damper and adjust as necessary DUCT DIAMETER in AREA sq ft 5 0 14 6 0 20 7 0 27 8 0 35 FORCED AIR FURNACE COOL AIR RETURN RETURN AIR 1 M 3 3 MIN RECOMMENDED UNIT IS NORMALLY BALANCED ON HIGH SPEED WITH FURNACE BLOWER ON OUTDOORS DUCTS CONNECTION MAY VARY DEPENDING ON MODEL 1 M 3 3 MIN RECOMMENDED NOTES 1 Furnace blower may be required to...

Страница 9: ...stem For these thermostats use the alternate control contacts wiring See Fig 27 Magnehelic Magnehelic OUTDOORS PLACE PITOT TUBE A MINIMUM OF 18 FROM BLOWER OR ELBOWS NOTE DUCT CONNECTIONS MAY VARY DEPENDING ON MODEL MAGNEHELIC GAGE PITOT TUBE PITOT TUBE MAGNEHELIC GAGE Pitot tube should be kept at least 12 in away from fans elbows and dampers to ensure accurate reading Fig 24 Pitot Tube Balancing ...

Страница 10: ...ering set the dehumidistat at its highest level and the switch on the HRV to standby If the Intellitek series controller is installed the air exchanger can be stopped at any time by turning the HRV off from the wall control However continuous ventilation is recommended Fall Rain and rapid temperature changes make it difficult to control the internal humidity level and may result in condensation on...

Страница 11: ...ated for life They require no maintenance Chassis The inside of the unit should be vacuumed yearly Be careful not to damage any of the mechanical compo nents and electrical connections Condensation Panel The condensation panel should be cleaned yearly Drain and Drain Line Units with drain lines should have their line and connection checked regularly Outside Hoods The outside hoods need to be check...

Страница 12: ... clean core House grilles closed or blocked Check and open grilles Dampers are closed if installed Check and open dampers Poor power supply at site Have electrician check supply voltage at house Ductwork is restricting HRV operation Check duct installation Improper speed control setting Increase the speed of the HRV HRV airflow improperly balanced Have contractor balance HRV Supply Air Feels Cold ...

Страница 13: ...BLE FOR 1 Normal maintenance as outlined in the installation and servicing instructions or owners manual including cleaning and or replacement of filters media or electronic cells 2 Damage or repairs required as a consequence of faulty installation or application by others 3 Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or inter...

Страница 14: ......

Страница 15: ......

Страница 16: ...inue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P707 5SI CARRIER CORPORATION 2004 4 04 REPLACES New PRINTED IN U S A CATALOG NUMBER 570 332 ...

Отзывы: