8.7 Operation hours switchover
In this image, the operating hours of the two indoor units are displayed and with the Function On / Off
the hours of operation change-over is activated / deactivated. The switching time and the time
remaining until the changeover takes place, is shown. To make a change, you have to press the ESC
button for 5 seconds. The cursor jumps to the input fi eld and with pressing the OK button, the fi eld is rea-
dy for input. To change values and to change fi elds, it has to be navigated with the cursor. The modifi ed
value must be confi rmed with OK. Leaving from the input function is performed by pressing the ESC key.
Thus, the inputs are activated.
8.8 Temperature stage function
With this image, the parameters of the temperature-dependent switch and the release are defi ned. By
Function On / Off this switching can be enabled / disabled. At higher or lower temperature, the second
indoor unit is connected or disconnected. The actual temperature value is also displayed. The procedure
to carry out changes, has been described in section 8.7.
ON:
Temperature at which the unit 2 is turned on
OFF:
Temperature at which the unit 2 is turned off
Hours
Remaining
time
Function
On/Off
switchover
time
Current
temperature
Setpoints
Function
On/Off
ON and OFF
Содержание TCB-ACREDU1-E
Страница 2: ...2 I TOSHIBA VERSION E ...
Страница 26: ...26 I TOSHIBA ...
Страница 27: ...TOSHIBA I 27 8 19 Circuit diagram ...
Страница 28: ...28 I TOSHIBA 8 20 Declaration of conformity ...
Страница 30: ...30 I TOSHIBA ...
Страница 31: ...TOSHIBA I 31 ...
Страница 32: ...AIR COND Klimaanlagen Handelsgesellschaft m b H Haushamer Straße 2 A 8054 Graz Seiersberg www air cond com ...