- 83 -
Error code causes and solutions. – part 4
Error code
(Hexadecimal)
Description
Cause
Required action
PWM board error
Replace PWM board
The power supply's voltage or frequency is outside the
specified working range.
Operate the unit within the specified working range.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
PWM board error
Replace PWM board
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
Compressor error
Replace compressor.
Miswiring and wiring disconnection of PWM board
Repair wiring.
Incorrect wiring or disconnection of compressor terminal Repair wiring.
The power supply's voltage or frequency is outside the
specified working range.
Operate the unit within the specified working range.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
Overload
Improve working conditions to reduce the load.
Compressor error
Replace compressor.
PWM board error
Replace PWM board
The power supply's voltage or frequency is outside the
specified working range.
Operate the unit within the specified working range.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
Load fluctuations are too large
Reduce fluctuations
Cooling fan error
Replace cooling fan.
A power outage occurred
Repair the power supply
Overload
Improve working conditions to reduce the load.
Compressor error
Replace compressor.
IPDU board error
Replace IPDU board
The power supply's voltage or frequency is outside the
specified working range.
Operate the unit within the specified working range.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
A power outage occurred
Repair the power supply.
Overload
Improve working conditions to reduce the load.
Cooling fan error
Replace cooling fan.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
Heat sink sensor error value
Repair wiring / change sensor.
PWM board error
Replace PWM board
Temperature sensor error
Replace temperature sensor.
PWM board error
Replace PWM board
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
Open circuit condition or loose connection in
communication line wiring.
Repair communication line.
Failure of communication port on EEV board
Replace EEV board
PWM board error
Replace PWM board
Blown 16A fuse (400 V specification only)
Rectify fault and replace 16A fuse.
Power rectifier error
Replace rectifier.
Open circuit condition in wiring
Repair wiring.
The power supply's voltage or frequency is outside the
specified working range.
Operate the unit within the specified working range.
PWM board error
Replace PWM board.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
A power outage occurred
Repair the power supply.
Circuit breaker has tripped
Rectify fault and switch breaker back on.
Rectifier for compressor error
Replace rectifier.
Blown fuse (400 V specification only)
Rectify fault and replace fuse.
Magnet switch breakdown
Replace magnet switch and repair wiring.
The power supply's voltage or frequency is outside the
specified working range.
Operate the unit within the specified working range.
PWM board error
Replace PWM board.
Open circuit condition or loose connection in control
wiring.
Repair the control wiring.
Heatsink sensor err
AD
B1
COMP IPDU board err
B0
COMP abnormal volt
COMP IPDU comm error
AF
Heatsink overheat
COMP Mortor Lock
A3
AC
A4
COMP Breakdown
A2
COMP Crnt snsr err
A5
COMP Other error
A1
COMP detct crcit err