- 33 -
The following tables show the data that is stored by each storage item.
Group Data 1
UC Data 1
Stored data
Symbol
Description
MC data
0_REMOTE Operating
pattern
0_PTN_NO Operation
pattern
System data
0_SYSNO* System number (0 to 15)
0_RUN*
Run/Stop
0_DND* Demand
0_MODNO* Operation
mode
number
0_SET*
Set temperature
0_FLWMD* Flow rate control method
0_CTRUC* Number of controllable UCs
0_ALMCD* Failure
codes
0_PSTG*
Number of operating pumps
0_UCSTG* Number of operating units
0_STAGE* Operating
capacity
0_OAT*
Average outdoor air temperature
0_EWT*
Average inlet water temperature
0_LWT*
Average outlet water temperature
0_SYSET*
Load side return water temperature
0_SYSLT*
Load side feed water temperature
0_SFLW*
Load-side flow rate
0_FLOW*
Heat source side flow rate
0_HDP*
Actual DRP
0_VALVE*
DPR valve opening
0_CAP* Approximate
capacity
Stored data
Symbol
Description
UC data
*_REMOTE Unit/Remote
*_RUN
Run/Stop
*_THMCMD Thermo instruction
*_MODENO Operation mode number
*_SET
Set temperature
*_ALM
Failure code
*_STAGE
Operating capacity (%)
*_EWT
Inlet water temperature
*_LWT
Outlet water temperature
*_FLOW Flow rate
*_DGP# High
pressure
*_SGP# Low
pressure
*_CPRUN# Compressor
running
time
*_CPCNT# Compressor
running
count
UC Data 2
Stored data
Symbol
Description
UC data
*_ALT
Alert code
*_CWT Middle water temperature
*_MMX
Pump frequency
*_EWP Inlet pressure
*_LWP
Outlet pressure
Group Data 2
Stored data
Symbol
Description
System data
0_FLWST* Flow rate control setting ID
0_GRPUC* Number of UC belonging to system
0_ALTCD* Alert
code
0_RPSTG* Required number of pumps
0_RQSTG* Required number of operating units
0_RQTHM* Thermo
requirement
0_RQFLW* System target flow rate
0_RQPMP* Pump instruction (0: Hz/1: flow rate)
0_DTFLW*
Design temperature differential
target flow rate
0_RQPFQ* Required
pump
Hz/frequency
0_RQHDP* Target differential pressure
04. Data&Time setting screen
• Select "04. Data&Time setting" from
. The screen on the
left appears.
• You can change the item with
and
. You can change
the numeric value with
and
.
05. LCD settings screen
• Select "05. LCD setting" from
. The screen on the left
appears.
• Press
and
to switch the
"
Backlight
"
and
"
Contrast
"
.
You can change the item with
and
.