- 60 -
11.
List of error codes
In the event of a fault, the error log of the module controller and the LED display on unit controller provide a
description of the fault. The LED display on the operation panel (unit controller) shows the fault code and the
name of the fault-causing circuit. The module controller shows the date and time when the fault occurred, the
failed module and circuit names, error code and its description.
In the event of a fault, the circuit name appears in the LED display on the unit controller operation panel. The digit
"0" in the circuit name position denotes the entire module; the letter "A" denotes Circuit A, the lowercase "b"
denotes Circuit B, the letter "C" denotes Circuit C, and the lowercase "d" denotes Circuit D. The letters "C" and
"A" also signify a failure of the upstream unit (Circuits C and D) and the downstream unit (Circuits A and B)
respectively.
Error code
(Hexadecimal)
Item
Description
Circuit name
displayed
Stop process
00
Normal
Normal
0
None
03
Phase loss error
Power phase loss is detected.
0
Applicable circuit
04
Output voltage error
EEV blown fuse
0
Applicable circuit only
05
Pump inverter overcurrent protection
operation (Note 1)
If pump inverter detects overcurrent
0
Applicable module
06
Pump inverter overvoltage protection
operation (Note 1)
If pump inverter detects overvoltage
0
Applicable module
07
Pump inverter overload protection
operation (Note 1)
If pump inverter detects overload
0
Applicable module
08
Pump inverter overheat protection
operation (Note 1)
If pump inverter detects overheat at heat sink
0
Applicable module
0A
Pump inverter motor overload
protection operation (Note 1)
If pump inverter detects motor overload
0
Applicable module
0C
Pump inverter low voltage protection
operation (Note 1)
If pump inverter detects low voltage
0
Applicable module
0D
Pump inverter output loss of phase
protection operation (Note 1)
If pump inverter detects output loss of phase
0
Applicable module
0E
Pump inverter other protection
operation (Note 1)
If pump inverter detects error other than those listed above
0
Applicable module
0F
Pump inverter communication error
(Note 1)
If the inverter does not respond to communication from the CPU board
0
Applicable module
10
Module controller, unit controller
communication error
Control board communication error
(between module controller and unit controller)
0
Note 2
12
Internal communication fault
If EEV does not respond to communication from the CPU board
A,C
Applicable module
1A
HIF board communication error
Data cannot be received between CPU board and HIF board
0
Operation continues only in the case of error output
1B
IO board communication error
If IO board does not respond to communication from the CPU board
0
Applicable module
20(Note3)
Thermistor error (chilled (warm)
water entering temperature)
Disconnection, shorting, or loose connection of applicable thermistor
C
Only two circuits on the upstream side
21(Note3)
Thermistor error (chilled (warm)
water leaving temperature)
Disconnection, shorting, or loose connection of applicable thermistor
A
Only two circuits on the downstream side
22(Note3)
Thermistor error (chilled (warm)
water middle temperature)
Disconnection, shorting, or loose connection of applicable thermistor
C
Only two circuits on the upstream side
2E
Relative humidity sensor error
(Note 4)
Disconnection, shorting, or loose connection of applicable thermistor
0
Operation continues only in the case of error output
2F
Thermistor error
(outside air temperature)
Disconnection, shorting, or loose connection of applicable thermistor
0
* Acquire outside air temperature from another module
and continue operation of the applicable module.
* If the temperature cannot be acquired from another
module, stop the applicable module.
30
Thermistor error (compressor
discharge gas temperature)
Disconnection, shorting, or loose connection of applicable thermistor
Name of applicable
circuit
Applicable circuit only
31
Thermistor error (compressor
suction gas temperature)
Disconnection, shorting, or loose connection of applicable thermistor
Name of applicable
circuit
Applicable circuit only
32
Thermistor error (coil gas
temperature 1) (Note 5)
Disconnection, shorting, or loose connection of applicable thermistor
Name of applicable
circuit
Applicable circuit only
33
Thermistor error (coil gas
temperature 2) (Note 5)
Disconnection, shorting, or loose connection of applicable thermistor
Name of applicable
circuit
Applicable circuit only
35
Thermistor error (reactor
temperature)
Disconnection, shorting, or loose connection of applicable thermistor
Name of applicable
circuit
Applicable circuit only Operation continues and only
error output is performed.
40
High-pressure sensor error
Disconnection, shorting, or loose connection of the applicable sensor
Name of applicable
circuit
Applicable circuit only
41
Low-pressure sensor error
Disconnection, shorting, or loose connection of the applicable sensor
Name of applicable
circuit
Applicable circuit only
4A
Water inlet pressure sensor error
Disconnection, shorting, or loose connection of the applicable sensor
0
Applicable module
4B
Water outlet pressure sensor error
Disconnection, shorting, or loose connection of the applicable sensor
0
Applicable module
4C
Pump suction press sensor err
Disconnection, shorting, or loose connection of the applicable sensor
0
Operation continues only in the case of error output
50 (Note 7)
Freeze prevention operation
triggered
Chilled/warm water outlet temperature is 2ºC or less.
Name of applicable
circuit
Only the two circuits connected to the applicable heat
exchanger
51
High temperature prevention
operation triggered
Chilled/warm water outlet temperature is 60ºC or more.
Name of applicable
circuit
Only the two circuits connected to the applicable heat
exchanger
52(Note7)
Low flow rate protection operation
triggered
Flow rate of applicable module is 100 L/min or less.
0
Applicable module
53
Water temperature inlet/outlet
reversal
Water temperature reversal in inlet and outlet,
with a difference of 2ºC or more sustained for one minute
0
Applicable module
5A
Subnormal pump suction press
Continue for 1 minute with pump suction pressure of less than -40 kPa
during pump operation
0
Applicable module
5B
Chilled (warm) water pressure rise
protection operation
Chilled (warm) water inlet pressure is 1 MPa or more.
0
Applicable module
60
High pressure cut
High-pressure switch (4.15MPa) is triggered.
Name of applicable
circuit
Applicable circuit only