- 34 -
06. Password setting screen
• Select "06. Password setting" from
. The screen on the left
appears.
• The password must be 4 digits. Choose a number between
0000 and 9999.
• You can change the digits with
and
.
• You can change the numeric value with
and
.
• When you press , a confirmation screen appears if there
are any changes.
• Refer to "When confirming on the message screen" for detailed
information about using the confirmation screen.
07. DN code setting screen
• Select "07. DN code setting" screen from
. The screen on
the left appears.
• You can change the DN code number with
.
• Press
according to the DN code number you want to
change. The data entry screen appears.
• Refer to the "Value input" screen for detailed information about
entering data.
• When you press , a confirmation screen appears if there
are any changes.
• Refer to "When confirming on the message screen" for detailed
information about using the confirmation screen.
List of the DN Codes (MC)
●
: Restarts when set
▲
: Items that can be displayed (can be set) as custom options
○
: Items that can be set by the user (standard)
DN
code
Description
Initial
value Min. Max.
Description
14
Continue operation when
GC communication failure
occurs
1
−
1 1
Set whether to continue operation in case of failure in communication with GC.
−
1: System operation stopped
0: Thermo OFF (minimum number of pumps operating)
1: System continued operation
42 System A: Failure setting at
POFF
0 0 1
Set whether to treat it as a failure if system A pump stops during pre-operation.
0: Do not treat as failure
1: Treat as failure
43 System A: Ratio of units with
major failures confirmed (%) 100
1
100 Set the failure ratio of UC for system A with major failure confirmed.
44
System A: Operation
continues when a major
failure occurs
2 0 2
Set whether to continue operation when system A has a major failure.
0: If the ratio of units with major failures confirmed is exceeded, stop operation
1: If all UCs have major failures, stop operation
2: Even when all UCs have major failures, MC continues operation and UC resumes
operation after recovery
45 System A: Pump
pre-operation time (sec)
15
10
180 Set the pump pre-operation time of system A.
46 System A: Pump remaining
operation time (sec)
15
10
180 Set the pump remaining operation time of system A.
82 System B: Failure setting at
POFF
0 0 1
Set whether to treat it as an failure if system B pump stops during pre-operation.
0: Do not treat as failure
1: Treat as failure
83 System B: Ratio of units with
major failures confirmed (%) 100
1
100 Set the failure ratio of UC for system B with major failure confirmed.
84
System B: Operation
continues when a major
failure occurs
2 0 2
Set whether to continue operation when system B has major failure.
0: If the ratio of units with major failures confirmed is exceeded, stop operation
1: If all UCs have major failures, stop operation
2: Even when all UCs have major failures, MC continues operation and UC resumes
operation after recovery
85 System B: Pump
pre-operation time (sec)
15
10
180 Set the pump pre-operation time of system B.
86 System B: Remaining pump
operating time (sec)
15
10
180 Set the pump remaining operation time of system B.