– 26 –
Interface P.C. board function setting exchange table
When operating the SW, turn off the power before setting.
The specifications of Terminal DO1 to DO6
The specifications of Terminal DO1 to DO6 are as follows.
• Use the contact side of the relay terminal used in TCB-IFDMR01UP-E according to the specifications shown in the
table below.
SW
Bit
Function Name
OFF
(Default)
ON
D
etail
SW501
1
No function
-
-
-
2
TA / TF type switching
TA type
TF type
The default is TA type. For TF type, turn on Bit2. If
Bit3 is ON, the Bit2 setting is invalid.
3
DDC type switching
No
function
DDC type
For DDC type, turn on Bit3.
4
DDC capacity control
Stepped
Linear
Change the capacity control method at 0 - 10 V.
Refer to the functions of AI3.
SW502
1
No function
-
-
-
2
3
4
Forced capacity control
None
Controlled
Refer to the functions of DI2 / DI2 ~ DI4 / DI4.
SW503
-
Output signal selection
(RSW)
-
-
Refer to the functions of DO5 / DO5 and DO6 /
DO6.
SW504
-
-
-
SW505
1
DI1 input inversion
Close
Open
Refer to the functions of DI1.
2
No function
-
-
-
3
4
SW506
1
Modbus baud rate
Refer to right table
2
3
No function
-
-
-
4
No function
-
-
-
SW507
1
Modbus address setting
(RSW)
-
-
Refer to “Modbus setting method” in this
installation manual.
SW701
1
Voltage / non-voltage
switching SW
Voltage
Non-voltage Refer to the functions of DI1 / DI1.
SW801
1
RS-485 terminating
resistance setting
Open
120 ohm
Refer to “Modbus setting method” in this
installation manual.
2
No function
-
-
-
TCB-IFDMX01UP-E
(Terminal block without relay)
TCB-IFDMR01UP-E
(Terminal block with relay)
Relay model name
Contact rating
Load conditions
G2RV-SR700-12DC
250 V max / 3 A max
(Minimum Current: 10 mA more)
Resistive load
Bit1
Bit2
Baud rate
OFF
OFF
9600
ON
OFF
19200
OFF
ON
38400
ON
ON
57600
DO1 - DO6
DO1 - DO6
MAX. 2 m
GND
Locally procured
DC12 V
Relay (DC12 V)
DO1 - DO6
11
14
DO1 - DO6
Locally procured
26-EN