– 39 –
NOTE
The following changes are settings to be configured by installation and service personnel.
If they are set incorrectly, trouble such as the product becoming inoperable may occur.
Set the following DN code according to the horsepower of the Dx-coil interface and the model name of the Valve kit.
1. Dx-coil interface horsepower (HP)
* Only outdoor units that support TU2C-LINK can be set.
2. Valve kit type name specification (This is basically set automatically).
Notice code signal setting (Terminal DI4 / DI4: Notice code Input)
Notice code is a function dedicated to TU2C-Link communication.
[Function]
• Enter the Notice code when you want to report an abnormality that does not stop the air conditioner from the outside.
• Used by switching functions with settings of Code No. (DN Code).
• Notice code is continuously issued while input signal is ON.
• 201 is displayed in the Notice code history when there is input in DI4.
[Setup method]
* Set data corresponding to Notice code to be used to one of Code No. 180 to 189, in accordance with following table.
In case where data other than 0000 is already set, set to other Code No. (DN Code).
*1: Refer to the Service Manual for support.
* It may take up to ten minutes to be displayed on remote controller after Notice code is issued.
7
When all the settings have been completed, push
ON/OFF button to finish the settings. (Return to the
normal mode)
“
” flashes and then the display content disappears
and the air conditioner enters the normal stop mode. (The
remote controller is unavailable while “
” is flashing.)
• To change settings of another indoor unit, repeat from
Procedure
1
.
Dx-coil capacity
8HP
10HP
12HP*
14HP*
16HP
18HP
20HP
Capacity code (DN11)
0021
0023
0024
0025
0026
0027
0028
Dx-coil capacity
24HP*
28HP*
32HP
34HP*
36HP
38HP*
40HP
Capacity code (DN11)
0031
0047
0035
0048
0037
0049
0039
Valve kit model
RBM-A101UPVA-E
RBM-A201UPVA-E
Code (DN) 4AE
0001
0002
Code No. (DN)
Set data
Notice code display
0180 ~ 189
0000
None (Factory default)
0129
201 (DI4 / DI4 Notice input ON)
0134
206 (Tx sensor*¹ trouble)
39-EN
Содержание RBM-A101UPVA-E
Страница 45: ...1134480001 ...