– 30 –
Terminal DI2 / DI2: External trouble Input
• An AHU fan operation monitor (Field supply), could be attached at this dry contact terminal (For example, the
abnormality of the fan motor). A closed contact generates the check code L30.
Terminal DI3 / DI3: Forced thermostat OFF Input
• When signal input, AHU is in “thermostat-off” status forcibly.
Terminal DI4 / DI4: Notice code Input
• If there is input, a spanner mark will be displayed on the remote controller. The system will not stop.
Check “DN settings” for the setting method.
Terminal DI5 / DI5: Operation Mode Input (Cool / Heat)
• Cool / Heat mode selection over a dry contact.
If the contact is short-circuited, system changes to heat mode.If the contact is open, system changes to cool mode.
• Only cool mode and heat mode are available.
When Bit4 of SW502 is turned on in DDC type, capacity demand can be achieved by short-circuiting Terminals DI2 to
DI4.
* If all are short-circuited, the DI3 function has priority.
When SW701 is ON (no voltage), apply a voltage of DC12 V ± 10% and wiring as follows.
Terminal DI6 / DI6: External ON/OFF Input
• When using with DDC, it starts by turning on this terminal.
Function
Terminal
OPEN
SHORT
Mode Input Cool / Heat
DI5 / DI5
COOL mode active
HEAT mode active
Short - circuit
Cooling step
Heating step
DI2
-
DI2
2
4
DI3
-
DI3
5
9
DI4
-
DI4
11
13
TCB-IFDMX01UP-E
(Terminal block without relay)
TCB-IFDMR01UP-E
(Terminal block with relay)
DI2 - DI4
DI2 -
DI4
MAX. 1 m
Locally procured
SIGNAL (+)
Signal Voltage (DC12 V ± 10%)
SIGNAL (-)
GND
Normally open
(+)
(-)
DI6
DI6
MAX. 100 m
Locally procured
(Input, DC5 V)
Relay coil signal
Same as on the left
30-EN