– 7 –
■
Installation Location
WARNING
Install the outdoor unit in a location that can
support the weight of the outdoor unit.
Insufficient durability may cause the outdoor unit to
fall, which may result in injury.
CAUTION
Do not install the outdoor unit in a location that
is subject to combustible gas leaks.
Accumulation of combustible gas around the
outdoor unit may cause a fire.
Install the outdoor unit in a location that meets
the following conditions.
•
A well-ventilated location free from obstacles near
the air inlets and air outlet
•
A location that does not increase the operating
noise or vibration of the outdoor unit
•
A location that does not produce any drainage
problems from discharged water
•
Location with easy access to power.
Do not install the outdoor unit in the following
location.
•
A location with a saline atmosphere (coastal area)
or one that is full of sul
fi
de gas (hot-spring area)
(Special maintenance is required.)
•
A location subject to oil, vapor, oily smoke, or
corrosive gases
•
A location in which organic solvent is used
•
A location where high-frequency equipment
(including inverter equipment, private
power generator, medical equipment, and
communication equipment) is used (Installation in
such a location may cause malfunction of the air
conditioner, abnormal control or problems due to
noise from such equipment.)
•
A location in which the discharged air of the
outdoor unit blows against the window of a
neighboring house
•
A location where the operating noise of the
outdoor unit is transmitted.
•
When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
•
A location in which drain water poses any
problems.
When an outdoor unit is installed in a location that
is always exposed to strong winds like a coast
or on the high stories of a building, one of the
following is recommended.
•
Install the unit so that its discharge faces the wall of
the structure.
Keep a distance 19.7” (500 mm) or more between
the unit and wall.
19.7" (500 mm)
•
Install the unit so that the discharge is at a right
angle relative to the wind direction.
Strong wind
Strong wind
•
Use wind baf
fl
e. Produce those parts in the
fi
eld.
•
When outside temperature conditions are 23°F
(-5°C) or lower and unit is running in cooling mode.
<Example>
Wind baf
fl
e
Wind baf
fl
e
■
Necessary space for
installation
Unit: in (mm)
Barrier at rear side
▼
Upper side is free
1. Single unit installation
5.9” (150)
or more
2. Barrier on right, left and rear.
7.9” (200)
or more
5.9” (150)
or more
The height of the
barrier should be
lower than the height
of the outdoor unit.
11.8” (300) or more
3. Multiple units installation
7.9” (200) or more
5.9”
(150)
or more
11.8”
(300)
or more
11.8”
(300)
or more
11.8”
(300)
or more
The height of the obstacle should be lower than the
height of the outdoor unit.
▼
Barrier also above unit
5.9” (150)
or more
19.7” (500)
or more
Barrier in front
▼
Above unit is free
1. Single unit installation
19.7”(500)
or more
2. Multiple units installation
39.4” (1000)
or more
▼
Barrier also above unit
39.4” (1000)
or more
39.4” (1000)
or more
13-EN
14-EN
1131601101 EN FR ES.indb 7
1131601101 EN FR ES.indb 7
4/8/2565 BE 10:14