Refrigerant Piping Connection

CAUTION

TAKE NOTE OF THESE 4 IMPORTANT POINTS 
BELOW FOR PIPING WORK 

1.

Keep dust and moisture away from inside the 
connecting pipes. 

2.

Tightly connect the connection between pipes and 
the unit. 

3.

Evacuate the air in the connecting pipes using a 
VACUUM PUMP. 

4.

Check for gas leaks at connection points. 

Piping connection

Flaring

1.

Cut the pipe with a pipe cutter. 
Be sure to remove burrs that may cause a gas leak. 

2.

Insert a flare nut into the pipe, and then flare the 
pipe. 
Use the flare nuts supplied with the air conditioner 
or those for R410A. 
Insert a flare nut into the pipe, and flare the pipe. 
As the flaring sizes of R410A differ from those of 
refrigerant R22, the flare tools newly manufactured 
for R410A are recommended. 
However, the conventional tools can be used by 
adjusting the projection margin of the copper pipe.

Projection margin in flaring : B (Unit : mm) 

Rigid (Clutch type) 

Flaring diameter size : A (Unit : mm)

* In case of flaring for R410A with the conventional flare 

tool, pull the tool out approx. 0.5 mm more than that 
for R22 to adjust it to the specified flare size.
The copper pipe gauge is useful for adjusting the 
projection margin size.

Liquid side

Outer diameter

Thickness

Ø9.5 mm

0.8 mm

Gas side

Outer diameter

Thickness

Ø15.9 mm

1.0 mm

Outer diam. of 

copper pipe

R410A tool 

used

Conventional 

tool used

R410A

1.0 to 1.5

9.5

0 to 0.5

15.9

Outer diam. of copper 

pipe

A

9.5

13.2

15.9

19.7

B

A

+0

–0.4

„

Tightening of Connecting Part

1.

Align the centers of the connecting pipes and fully 
tighten the flare nut with your fingers. Then fix the 
nut with a wrench as shown in the figure and tighten 
it with a torque wrench.

2.

As shown in the figure, be sure to use two wrenches 
to loosen or tighten the flare nut of the valve on the 
gas side. If you use a single crescent, the flare nut 
cannot be tightened to the required tightening 
torque.
On the other hand, use a single crescent to loosen 
or tighten the flare nut of the valve on the liquid side.

(Unit: N•m)

CAUTION

1.

Do not put the crescent wrench on the cap or cover. 
The valve may break. 

2.

If applying excessive torque, the nut may break 
according to some installation conditions. 

• After the installation work, be sure to check for gas 

leaks of the pipe connections with nitrogen. 

• Pressure of R410A is higher than that of R22 (Approx. 

1.6 times). 
Therefore, using a torque wrench, tighten the flare 
pipe connecting sections that connect the indoor/
outdoor units at the specified tightening torque. 
Incomplete connections may cause not only a gas 
leak, but also trouble with the refrigeration cycle. 

Outer dia. of copper pipe

Tightening torque

9.5 mm (diam.)

33 to 42 (3.3 to 4.2 kgf•m)

15.9 mm (diam.)

63 to 77 (6.3 to 7.7 kgf•m)

Half union or packed valve

Flare nut

Externally 
threaded side

Internally 
threaded side

Fix with wrench.

Tighten with torque wrench.

Cover

Piping valve

Tightened

Flare nut

Cap

Loosened

Valve at gas side

Do not apply refrigerant oil to the flared surface. 

NO GOOD

Cover

Cap

Содержание RAV-SP1104AT-A

Страница 1: ...English AIR CONDITIONER SPLIT TYPE Installation manual Outdoor Unit Model name RAV SP1104AT A RAV SP1404AT A For commercial use ...

Страница 2: ...ual describes the installation method of the outdoor unit For installation of the indoor unit follow the Installation Manual attached to the indoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type that has adopted a new refrigerant HFC R410A instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer 1 ACCESSORY PARTS Accessory Parts Part name ...

Страница 3: ...he unit falling If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a cooking range noxious gas may be generated Electrical work ...

Страница 4: ...ewly for R410A only Charging hose Prepared newly for R410A only Charging cylinder Can not be used Unusable Use the refrigerant charging measure instead Gas leak detector Gas leak check Prepared newly Vacuum pump Vacuum drying Unusable Vacuum pump with backflow prevention function Vacuum drying R22 Conventional tools Refrigerant Piping New refrigerant R410A When using the conventional piping When u...

Страница 5: ...le enough to support the weight of the outdoor unit Insufficient durability may cause the outdoor unit to fall which may result in injury CAUTION Do not install the outdoor unit in a location that is subject to combustible gas leaks Accumulation of combustible gas around the outdoor unit may cause a fire Install the outdoor unit in a location that meets the following conditions after the customer ...

Страница 6: ...0 or more 300 or more 300 or more The height of the obstacle should be lower than the height of the outdoor unit 200 or more 150 or more 500 or more Obstacle in front Above unit is free 1 Single unit installation 2 Serial installation of two or more units Obstacle also at the above unit Obstacles in both front and rear of unit Open above and to the right and left of the unit The height of an obsta...

Страница 7: ...tion proof rubber pads Foundation GOOD Bottom plate of outdoor unit Foundation Support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit NO GOOD If only the end of the fixing leg is supported it may deform Do not support the outdoor unit only with the fixing leg Foundation 15 or less Drain nipple Waterproof rubber cap 5pcs Waterproof r...

Страница 8: ... 5 15 9 Outer diam of copper pipe A 9 5 13 2 15 9 19 7 B A 0 0 4 Tightening of Connecting Part 1 Align the centers of the connecting pipes and fully tighten the flare nut with your fingers Then fix the nut with a wrench as shown in the figure and tighten it with a torque wrench 2 As shown in the figure be sure to use two wrenches to loosen or tighten the flare nut of the valve on the gas side If y...

Страница 9: ...o discharge the air nitrogen etc that remains in the set If air remains the capacity may decrease For the vacuum pump be sure to use one with a backflow preventer so that the oil in the pump does not backflow into the pipe of the air conditioner when the pump stops If oil in the vacuum pump is put in an air conditioner including R410A it may cause trouble with the refrigeration cycle Vacuum pump P...

Страница 10: ...r or less refrigerant pipe Valve unit Charge port Using a minus screwdriver turn it counterclockwise by 90 until it hits the stopper Full open Flare nut Handle position Closed completely Opened fully Main stopper Movable part of valve Stem Stopper pin Valve size Ø9 5 mm 33 to 42 N m 3 3 to 4 2 kgf m Ø15 9 mm 20 to 25 N m 2 0 to 2 5 kgf m Charge port 14 to 18 N m 1 4 to 1 8 kgf m 31 75 m L 40 g L 3...

Страница 11: ...A switch that disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring Model RAV SP110 SP140 Power supply 220 240 V 50 Hz Maximum running current 22 8 A Installation fuse rating 25 A all types can be used Power wire H07 RN F or 60245 IEC 66 2 5 mm2 or more Indoor outdoor connecting wires H07 RN F or 60245 IEC 66 1 5 mm2 or more L N 1 2 3 1 2 3 Ma...

Страница 12: ...ervice person Failure to clean the indoor outdoor units regularly will result in poor performance icing water leaking and even compressor failure 12 FUNCTIONS TO BE IMPLEMENTED LOCALLY Night operation control Low noise operation is available during nighttime hours by connecting a commercially available timer and separately sold applicable control wire TCB KBOS1E For more information refer to the m...

Страница 13: ...the Installation Manual of the indoor unit Verifying current abnormal status 1 Check that DIP switch SW803 is set to OFF 2 Jot down the states of LED800 to LED804 Display mode 1 3 Press SW800 for at least 1 second The LED status changes to display mode 2 4 Check the code whose display mode 1 equals the LED states jotted down and display mode 2 equals the current flashing status of LED800 to LED804...

Страница 14: ...n the existing pipe thickness is thinner than the specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works The operating pressure of R410A is high 1 6 times that of R22 and R407C If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thic...

Страница 15: ...g pipe Re machine the flare machining size to size for R410A In case that a gas pipe Ø19 mm or bigger is used for the outdoor unit of SP80 3 HP Our R410A model 3 to 5 HP gas pipe size is Ø15 9 mm After the existing air conditioner is operated in cooling mode for approx 30 minutes or longer recover the refrigerant For cleaning the pipes and recovering oil Refrigerant recovery Pump down method Airti...

Страница 16: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg Total amount of refr...

Отзывы: