- 14 -

8.

When temporary installation and removal of the air 
conditioner are repeated such as when leased etc.

9.

If the type of refrigerator oil of the existing air 
conditioner is other than the following oil (Mineral 
oil), Suniso, Freol-S, MS (Synthetic oil), alkyl 
benzene (HAB, Barrel-freeze), ester series, PVE 
only of ether series.
• The winding-insulation of the compressor may 

deteriorate.

NOTE

The above descriptions are results have been confirmed 
by our company and represent our views on our air 
conditioners, but do not guarantee the use of the existing 
pipes of air conditioners that have adopted R410A in 
other companies.

Branching pipe for simultaneous operation 
system

• In the concurrent twin system, when TOSHIBA has 

specified that branching pipe is to be used, it can be 
reused.
Branching pipe model name: 
RBC-TWP30E2, RBC-TWP50E2 
On the existing air conditioner for simultaneous 
operation system (twin system), there are cases of 
branch pipes being used that have insufficient 
compressive strength.
In such case, please change the piping to a branch 
pipe for R410A. 

Curing of pipes

When removing and opening the indoor or outdoor unit 
for a long time, cure the pipes as follows:
• Otherwise rust may be generated when moisture or 

foreign matter due to condensation enters the pipes.

• The rust cannot be removed by cleaning, and new 

pipes are necessary. 

Placement 

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 

month

Pinching or 

taping 

Indoors

Every time 

H

A

Nitrogen gas pressure 0.5 Mpa

Existing pipes: Cannot be used. 
• Use new pipes.

Connect the indoor/outdoor units to the existing pipe. 
• Use a flare nut attached to the main unit for the 

indoor/outdoor units. (Do not use the flare nut of the 
existing pipe.)

• Re-machine the flare machining size to size for R410A.

In case that a gas pipe 

Ø

19 mm or bigger is used for the 

outdoor unit of SP80 (3 HP): (Our R410A model 3 to 5 HP 
gas pipe size is 

Ø

15.9 mm)

•  After the existing air conditioner is operated in cooling 

mode for approx. 30 minutes or longer,* recover the 
refrigerant.

•  For cleaning the pipes and recovering oil

•  Refrigerant recovery: Pump down method

•  (Airtight test), Vacuum dry, Refrigerant charge, Gas leak 

check

• Remove the existing air conditioner from the piping and 

carry out flushing (nitrogen pressure 0.5 Mpa) to remove 
any remains inside of the pipe.

Was largely discolored oil or a large quantity 

of remains discharged? (When the oil 

deteriorates, the color of the oil changes to a 

muddy or black color.)

(If there is discharge of remains, it is judged that a 
large quantity of remains are present.)

Piping necessary to change the flare nut/
machining size due to pipe compression

Clean the pipes or use new pipes.

In case of twin pipes, also be sure to flush the 
branching pipe.

Note]

Turn the existing pipe switch on the cycle control PC 
board of the outdoor unit to ON side. At shipment from 
factory OFF 

 ON for existing pipe (Refer to the table 

below.) (Be sure to set the contents in the table below 
in order to restrict the refrigerating cycle pressure of 
the equipment in the pipe standard.)

Existing pipe SW

Trial run

1) Flare nut width: H

2) Flare machining size: A

(mm)

(mm)

Becomes a little larger for R410A

For R410A

For R22

Copper pipe 
outer 
diameter

For R410A

For R22

Same as above

Same as 

above

Do not apply refrigerator oil to the flare surface.

Bit 3 of SW802 

ON 

4, 5 HP

 

 

Switch

Ø6.4

Ø9.5

Ø12.7

Ø15.9

Ø19.0

17

22

26

29

36

24

27

Ø6.4

Ø9.5

Ø12.7

Ø15.9

Ø19.0

9.1

13.2

16.6

19.7

24.0

9.0

13.0

16.2

19.4

23.3

 

Copper pipe 
outer 
diameter

 

NO

YES

YES

YES

NO

NO

Are there scratches or dents on the existing pipes?

Is it possible to operate the existing air conditioner?

EN-27

EN-28

Содержание RAV-SP1104AT-A

Страница 1: ...English AIR CONDITIONER SPLIT TYPE Installation manual Outdoor Unit Model name RAV SP1104AT A RAV SP1404AT A For commercial use ...

Страница 2: ...ual describes the installation method of the outdoor unit For installation of the indoor unit follow the Installation Manual attached to the indoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type that has adopted a new refrigerant HFC R410A instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer 1 ACCESSORY PARTS Accessory Parts Part name ...

Страница 3: ...he unit falling If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a cooking range noxious gas may be generated Electrical work ...

Страница 4: ...ewly for R410A only Charging hose Prepared newly for R410A only Charging cylinder Can not be used Unusable Use the refrigerant charging measure instead Gas leak detector Gas leak check Prepared newly Vacuum pump Vacuum drying Unusable Vacuum pump with backflow prevention function Vacuum drying R22 Conventional tools Refrigerant Piping New refrigerant R410A When using the conventional piping When u...

Страница 5: ...le enough to support the weight of the outdoor unit Insufficient durability may cause the outdoor unit to fall which may result in injury CAUTION Do not install the outdoor unit in a location that is subject to combustible gas leaks Accumulation of combustible gas around the outdoor unit may cause a fire Install the outdoor unit in a location that meets the following conditions after the customer ...

Страница 6: ...0 or more 300 or more 300 or more The height of the obstacle should be lower than the height of the outdoor unit 200 or more 150 or more 500 or more Obstacle in front Above unit is free 1 Single unit installation 2 Serial installation of two or more units Obstacle also at the above unit Obstacles in both front and rear of unit Open above and to the right and left of the unit The height of an obsta...

Страница 7: ...tion proof rubber pads Foundation GOOD Bottom plate of outdoor unit Foundation Support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit NO GOOD If only the end of the fixing leg is supported it may deform Do not support the outdoor unit only with the fixing leg Foundation 15 or less Drain nipple Waterproof rubber cap 5pcs Waterproof r...

Страница 8: ... 5 15 9 Outer diam of copper pipe A 9 5 13 2 15 9 19 7 B A 0 0 4 Tightening of Connecting Part 1 Align the centers of the connecting pipes and fully tighten the flare nut with your fingers Then fix the nut with a wrench as shown in the figure and tighten it with a torque wrench 2 As shown in the figure be sure to use two wrenches to loosen or tighten the flare nut of the valve on the gas side If y...

Страница 9: ...o discharge the air nitrogen etc that remains in the set If air remains the capacity may decrease For the vacuum pump be sure to use one with a backflow preventer so that the oil in the pump does not backflow into the pipe of the air conditioner when the pump stops If oil in the vacuum pump is put in an air conditioner including R410A it may cause trouble with the refrigeration cycle Vacuum pump P...

Страница 10: ...r or less refrigerant pipe Valve unit Charge port Using a minus screwdriver turn it counterclockwise by 90 until it hits the stopper Full open Flare nut Handle position Closed completely Opened fully Main stopper Movable part of valve Stem Stopper pin Valve size Ø9 5 mm 33 to 42 N m 3 3 to 4 2 kgf m Ø15 9 mm 20 to 25 N m 2 0 to 2 5 kgf m Charge port 14 to 18 N m 1 4 to 1 8 kgf m 31 75 m L 40 g L 3...

Страница 11: ...A switch that disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring Model RAV SP110 SP140 Power supply 220 240 V 50 Hz Maximum running current 22 8 A Installation fuse rating 25 A all types can be used Power wire H07 RN F or 60245 IEC 66 2 5 mm2 or more Indoor outdoor connecting wires H07 RN F or 60245 IEC 66 1 5 mm2 or more L N 1 2 3 1 2 3 Ma...

Страница 12: ...ervice person Failure to clean the indoor outdoor units regularly will result in poor performance icing water leaking and even compressor failure 12 FUNCTIONS TO BE IMPLEMENTED LOCALLY Night operation control Low noise operation is available during nighttime hours by connecting a commercially available timer and separately sold applicable control wire TCB KBOS1E For more information refer to the m...

Страница 13: ...the Installation Manual of the indoor unit Verifying current abnormal status 1 Check that DIP switch SW803 is set to OFF 2 Jot down the states of LED800 to LED804 Display mode 1 3 Press SW800 for at least 1 second The LED status changes to display mode 2 4 Check the code whose display mode 1 equals the LED states jotted down and display mode 2 equals the current flashing status of LED800 to LED804...

Страница 14: ...n the existing pipe thickness is thinner than the specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works The operating pressure of R410A is high 1 6 times that of R22 and R407C If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thic...

Страница 15: ...g pipe Re machine the flare machining size to size for R410A In case that a gas pipe Ø19 mm or bigger is used for the outdoor unit of SP80 3 HP Our R410A model 3 to 5 HP gas pipe size is Ø15 9 mm After the existing air conditioner is operated in cooling mode for approx 30 minutes or longer recover the refrigerant For cleaning the pipes and recovering oil Refrigerant recovery Pump down method Airti...

Страница 16: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg Total amount of refr...

Отзывы: