- 10 -
Wiring between Indoor Unit and
Outdoor Unit
The dashed lines show on-site wiring.
• Connect the indoor/outdoor connecting wires to the
identical terminal numbers on the terminal block of
each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the
following specifications.
How to wire
1.
Connect the connecting wire to the terminal as
identified with their respective numbers on the
terminal block of the indoor and outdoor units.
H07 RN-F or 60245 IEC 66 (1.5 mm
2
or more)
2.
When connecting the connecting wire to the outdoor
unit terminal, prevent water from coming into the
outdoor unit.
3.
Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
4.
For interconnecting wires, do not use a wire joined
to another on the way.
Use wires long enough to cover the entire length.
CAUTION
• An installation fuse must be used for the power supply
line of this air conditioner.
• Incorrect/incomplete wiring may lead to an electrical
fire or smoke.
• Prepare an exclusive power supply for the air
conditioner.
• This product can be connected to the mains power.
Fixed wire connections :
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in
the fixed wiring.
Model RAV-
SP110
SP140
Power supply
220-240 V~, 50 Hz
Maximum running
current
22.8 A
Installation fuse
rating
25 A (all types can be used)
Power wire
H07 RN-F or 60245 IEC 66
(2.5 mm
2
or more)
Indoor/outdoor
connecting wires
H07 RN-F or 60245 IEC 66
(1.5 mm
2
or more)
L
N
1
2
3
1
2
3
(Main circuit)
(Indoor/outdoor
connecting wires)
Outdoor
unit
Remote
controller
Indoor
unit
Earth
Circuit
breaker
Input power
220-240 V~,
50 Hz
Wiring diagram
* For details on the remote controller wiring/installation,
refer to the Installation Manual enclosed with the
remote controller.
Single system
Simultaneous twin system (SP140 type only)
Stripping length power cord and connecting
wire
A
B
1
1
L
N
2
2
3
3
Remote controller
Remote controller
wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
Power supply
A
B
1
2
3
A
B
1
1
L
N
2
2
3
3
Remote controller
Remote controller
wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
Power supply
Indoor
side
Remote
controller inter-
unit wiring
Indoor power
inter-unit wiring
L
N
1
2
3
Power supply
terminal block
To Indoor unit
terminal block
Earth screw
Earth screw
Connecting wire
Pipe valve
fixing plate
Power supply
wire
(mm)
10
10
L N
40
10
50
50
10
30
1 2 3
Earth line
Earth line
Connecting
wire
Power
supply wire
EN-19
EN-20