– 13 –
Filter sign setting
According to the installation condition, the filter sign
term (notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [01].
• For the [SET DATA] in Procedure
4
, select the SET
DATA of filter sign term from the following table.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [06].
• For the set data in Procedure
4
, select the SET
DATA of shift value of detection temperature to be
set up from the table below.
Power saving mode
◆
Performing settings of the power
saving mode
* When an outdoor unit RAV-SP***2AT / RAV-
SM***3AT or earlier is used, the power level is fixed
to 75 % regardless of the value on the display.
1
Push
button for 4 seconds or more
when the air conditioner is not working.
flashes.
Indicates CODE No. “C2.”
2
Select an indoor unit to be set by pushing
(left side of the button).
Each time the button is pushed, unit
numbers change as follows:
The fan of the selected unit runs.
3
Adjust the power save setting by pushing
TIME
/
buttons.
Each push of the button changes the power
level by 1 % within the range from 100 % to
50 %.
* The factory default is 75 %.
4
Determine the setting by pushing
button.
5
Push
button to complete the setting.
SET DATA
Filter sign term
0000
None
0001
150 H
(factory default)
0002
2500 H
0003
5000 H
0004
10000 H
SET DATA
Detection temperature shift value
0000
No shift
0001
+1 °C
0002
+2 °C
(factory default)
0003
+3 °C
0004
+4 °C
0005
+5 °C
0006
+6 °C
UNIT No.
1-1
UNIT No.
1-2
UNIT No.
1-3
UNIT No.
1-4
Setting of power level in
power saving mode
Remote controller switch
monitoring function
This function is available to call the service monitor
mode from the remote controller during a test run to
acquire temperatures of sensors of the remote
controller, indoor unit, and outdoor unit.
1
Push
and
buttons simultaneously for
at least 4 seconds to call the service monitor
mode.
The service monitor indicator lights up and
the header indoor unit number is displayed
first. CODE No.
is also displayed.
2
Pushing TEMP.
/
buttons, select the
number of sensor (CODE No.) to be
monitored. (See the following table.)
3
Pushing
(left side of the button),
select an indoor unit to be monitored. The
sensor temperatures of indoor units and
their outdoor unit in the control group are
displayed.
4
Push
button to return to the normal
display.
1
3
4
2
Indoor unit data
CODE
No.
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil) temperature
(TCJ)
04
Indoor unit heat exchanger (coil) temperature
(TC)
F3
Indoor unit fan cumulative operating hours (x1
h)
Outdoor unit data
CODE
No.
Data name
60
Outdoor unit heat exchanger (coil) temperature
(TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
64
—
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
F1
Compressor cumulative operating hours (x100
h)
25-EN
26-EN