8-3. Table Inspection of outdoor unit main parts
No.
Parts name
Checking procedure
1
Compressor
(Model :
RA330A2T-20M
)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
1.
20
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
2
Outdoor fan motor
(Model : WDF-340-A100-1)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
17.3±1.7
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
3
4-way valve coil
(Cooling/heating switching)
(Model : STF-H)
Measure the resistance value of each winding by using the tester.
Resistance value
7.1±0.36
Ω
Under 20°C
Connector : White
- 60 -