Model name
Outdoor unit
RAV-SM
1104AT
8
*
P
*
1404AT
8
*
P
*
Power supply
3 phase 380-415V, 50Hz
3 phase 380V, 60Hz
(Power exclusive to outdoor is required.)
Compressor
Type
Hermetic compressor
Motor
(kW)
2.5
3.0
Pole
4
4
Refrigerant charged
(kg)
2.8
2.8
Refrigerant control
Pulse motor valve
Inter
connecting pipe
Standard length
(m)
7.5
7.5
Min. length
(m)
5
5
Max. total length
(m)
50
50
Additional refrigerant charge
under long piping connector
40g/m
(31m to 50m)
40g/m
(31m to 50m)
Height
difference
Outdoor lower
(m)
30
30
Outdoor higher
(m)
30
30
Outer dimension
Height
(mm)
890
890
Width
(mm)
900
900
Depth
(mm)
320
320
Appearance
Silky shade (Muncel 1Y8.5/0.5)
Total weight
(kg)
6
9
6
9
Heat exchanger
Finned tube
Fan unit
Fan
Propeller fan
Standard air flow high
(m3/min.)
68
70
Motor
(W)
100
100
Connecting pipe
Gas side
(mm)
15.9
15.9
Liquid side
(mm)
9.5
9.5
Sound pressure level
Cooling/Heating (dB·A)
53/54
54/55
Sound power level
Cooling/Heating (dB·A)
70/71
70/71
Outside air temperature, Cooling
°C (Dry bulb temp.)
46 to -15
Outside air temperature, Heating
°C (Wet bulb temp.)
15 to -15
1. SPECIFICATIONS
1-1. Outdoor Unit
<Digital Inverter>
- 14 -
FILE NO. SVM-17005