24
Procedure
6
7
Description
If there is other indoor unit to be changed, repeat
Indoor unit No. before setup change is displayed.
procedure
2
to
5
to change the setup.
When the above setup has finished, push
UNIT
LOUVER
to
select the indoor unit No. before change of setup, specify
CODE No. [12], [13], [14] in order with temp. setup
/
buttons, and then check the changed contents.
Address change check Before change:
[3-3-1]
→
After change: [2-2-2]
Pushing
CL
button clears the contents of which setup was changed.
(In this case, procedure from
2
is repeated.)
After check of the changed contents, push
TEST
button. (Setup is determined.) When pushing
TEST
button, the
display disappears and the status becomes the usual stop status. (When pushing
TEST
button the operation from
the remote controller is not accepted for approx. 1 minute.)
* If the operation from the remote controller is not accepted even
1 minute or more passed after pushing
TEST
button, it is
considered that the address setup is incorrect.
In this case, the automatic address must be again set up.
Therefore repeat procedure of the setup change from the Procedure
1
.
To recognize the position of the corresponding
indoor unit though the indoor unit No. is known
Check the position during operation stop.
(Be sure to stop operation of the set.)
Procedure
1
2
3
Description
Push simultaneously
TEST
+
VENT
buttons for 4 seconds or more.
After a while, the display part flashes and the display appears as shown below.
In this time, the position can be checked because fan and louver of the indoor unit operate.
• For the group control, the indoor unit No. is displayed as [
] and
fans and louvers of all the indoor units in the group control operate.
Check the displayed CODE No. is [01].
• When the CODE No. is other than [01], push
TEST
button to
erase the display and repeat procedure from the first step.
(After pushing
TEST
button, operation of the remote controller
(
∗
Display changes according
is not accepted for approx. 1 minute.)
to the model No. of indoor unit.)
In the group control, every pushing
UNIT
LOUVER
button, the indoor unit No. in the group control is displayed in order.
In this time, the position of the indoor unit can be confirmed because only fan and louver of the selected indoor
unit operate. (For a group control, No. of the firstly displayed indoor unit becomes the header unit.)
After confirmation, push
TEST
button to return the mode to the
usual mode.
When pushing
TEST
button, the display disappears and the status
becomes the usual stop status.
(When pushing
TEST
button the operation from the remote controller
is not accepted for approx. 1 minute.)
1, 3
2
1
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER