OFF
HH
H
L
UL
E zone
D zone
C zone
B zone
A zone
T
C
, T
CJ
˚C
32
30
28
26
20
16
No.
6
7
Item
Fan speed control
(Continued)
Cold air draft
preventive control
Outline of specifications
3)
In heating operation, the
fan speed
changes to [UL] if
thermostat
is turned off.
4)
If T
A
≥
25°C when heating operation has started
or
defrost
operation has been cleared, the air conditioner
operates with
(H) mode or higher mode for
1 minute after Tc entered in E zone of
cold air draft preventive
control
(No. 7)
.
1) In heating operation, the indoor fan is controlled based on
the detected temperature of T
C
sensor or T
CJ
sensor. As
shown below, the upper limit of the
fan speed is restricted in
spite of the fan speed set on remote control.
However B zone is assumed as C zone for
6 minutes
after the compressor has started
.
In defrost operation, the control value of T
C
is shifted
+6
°C.
Remarks
In A zone while
thermostat
is ON,
[PRE-HEAT
(Heating ready)] is
displayed.
CODE No.
DN :
[
5d
]
SW501 (1)-(2)
TAP
HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL
F1
HH
HH
F2
HH
HH
H+
H+
F3
HH
HH
H+
H+
F4
HH
HH
HH
H+
H+
F5
HH
HH
H+
H+
H
H
F6
HH
H+
H+
H
H
L+
L+
F7
HH
HH
H+
H+
H
H
F8
H+
H+
H
H
H
H
L+
L+
L+
L+
F9
H
H
L+
L+
L+
L+
L
L
FA
H
H
L+
L+
L
L
L
L
FB
L+
L+
L
L
L
L
FC
L
L
L
L
FD
LL
LL
LL
LL
LL
LL
LL
LL
LL
LL
LL
LL
LL
LL
ON-ON
ON-OFF
-
-
OFF-OFF
-
OFF-ON
250Pa
0001
0002
0004
0000
0005
0003
0006
50Pa
83Pa
117Pa
150Pa
183Pa
217Pa
- 30 -