Item No. (DN) table (Selection of function)
DN
01
02
03
06
0F
10
11
12
13
14
19
1E
28
2A
2b
2E
30
31
32
33
Item
Filter sign lighting time}
Dirty state of filter
Central control address
Heating suction temp shift
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Louver type
(Air direction adjustment)
∗
None for concealed duct
Temp difference of
automatic cooling/heating
mode selection COOL
→
HEAT, HEAT
→
COOL
Auto restart after power
failure
Option
Thermo
stat
output
selection
(T10
e
)
Option
Option
Option
Sensor selection
Temperature indication
Description
0000 : None
0002 : 2500H (4-Way/Duct/Ceiling Type)
0000 : Standard
0001 : High degree of dirt
(Half of standard time)
0001 : No.1 unit
to
0064 : No.64 unit
0099 : Unfixed
0000 : No shift
0001 : +1°C
0002 : +2°C
to
0010 : –10°C
(Up to recommen 6)
0000 : Heat pump
0001 : Cooling only
(No display of [AUTO] [HEAT])
0004 : Concealed duct type
0007 : Ceiling type
0014 : Compact 4-way cassette type
0000 : Unfixed
000
9
:
56
type
00
12
:
80
type
00
15
:
110
type
001
7
:
140
type
0001 : No.1 unit
to
0030 : No.30 unit
0001 : No.1 unit
to
0064 : No.64 unit
0000 : Individual
0001 : Master of group
0002 : Follower of group
0000 : No louver
0001 : Swing only
0002 : 1-way
0003 : 2-way
0004 : 4-way
0000 : 0 deg
to
0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0001 : Auto restart
0000 :
Indoor
thermostat
ON
0001 :
Output of outdoor comp-ON receiving
0000 : Body TA sensor0001 : Remote controller sensor
0000 : °C (celsius)
0001 : °F (Fahrenheit)
At shipment
0002 : 2500H
0000 : Standard
0099 : Unfixed
0002 : +2°C
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to model type
0003 : 3 deg (Ts±1.5)
0000 : None
0002 : Default
0000: Thermo
stat
ON
0000 : Default
0000 : Default
0000 : Default
0000 : Body sensor
0000 : °C
42
Self clean time
0000: None
0001: 0.5h to 0.012: 6.0h
The case that compressor-ON time is 10 to 60 minutes is
set up. When ON time is over 60 minutes, the operating
time becomes two times of it.
0002: 60 minutes
40
Option
0003 : Default
- 72 -