– 19 –
Model name
Indoor Unit
RAV-RM
RAV-GP
561MUT-E
561ATP-E
Appearance
Main Unit
Zinc hot dipping steel plate
* Heat-insulating material attached to only upper plate
Air filter
Drain port (Nominal dia. mm)
Electrical
characteristics
(*1)
Cooling
Running current
A
Sound pressure level
Cooling/Heating
dB(A)
Sound power level
Cooling/Heating
dB(A)
Pipe connections
Gas / Liquid
mm
Min. Length
m
Operation Range
Cooling
˚C
Heating
˚C
Max. Length
m
Chargeless
m
Max. height difference
m
Weight
kg
Outer dimension
H x W x D
mm
Refrigerant ( Type / Charge weight (kg) )
R32/1.35
630 x 799 x 299
45
46 / 48
63 / 65
12.7 / 6.4
3
50
20
30
–15 to 52
–27 to 15
Sound pressure level High ( M+ / M / L+ / L )
dB(A)
Sound power level High ( M+ / M / L+ / L ) (*2)
dB(A)
Standard air flow ( M+ / M / L+ / L )
m³/h
Motor
W
Fan unit
Fan
Heat exchanger
Outer dimension Main unit
H x W x D (*3)
mm
Ceiling panel
(Sold Separately)
H x W x D (*3)
mm
12 x 620 x 620
Weight
Main unit
kg
15.0
2.5
Finned tube
Turbo fan
798 (720 / 672 / 562 / 546)
60
Standard filter (Long life filter)
VP20 (Polyvinyl chloride tube)
44 ( 42 / 39 / 36 / 35 )
59 ( 57 / 54 / 51 / 50 )
Ceiling panel (Sold Separately)
kg
Ceiling panel
(Sold Separately)
Model name
RBC-UM21PG(W)-E
Gran White (Mansell 5PB9/1)
256 x 575 x 575
Color
Power consumption
kW
Power factor
%
EER
Heating
Running current
A
Maximum current
A
Indoor Unit
Outdoor Unit
Power consumption
kW
Power factor
%
COP
Cooling capacity (Rated (Min.-Max.))
kW
5.0 (1.2-5.6)
5.6 (0.9-7.0)
1 phase 50Hz 230V (220V-240V)
7.49 - 6.87
1.56
94
3.21
7.68 - 7.04
1.60
95
3.5
13.1
Heating capacity (Rated (Min.-Max.))
kW
Power supply
Outdoor Unit
1. SPECIFICATIONS
SDI combination (R32)
<Single type>
*1 : The Cooling capacity and electrical characteristics are measured under the conditions specified by JIS B
8615-1 based on the reference piping.
The reference piping consists of 5m of main piping and 2.5m of branch piping connected with 0 meter
height.
*2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616. Normally, the
values measured in the actual operation environment become larger than the indicated values due to the
effects of external sound.
*3 : Height from the ceiling. Depth doesn't include the electric parts box.
Notes ;
Rated conditions Cooling : Indoor air temperature 27°CDB/ 19 °CWB, Outdoor air temperature 35°CDB
Heating : Indoor air temperature 20°CDB, Outdoor air temperature 7°CDB/ 6°CWB