– 43 –
No.
19
20
Item
DC motor
Power saving
Outline of specifications
1) When the fan operation has started, positioning of the
stator and the rotor are performed.
(Moves slightly with tap sound)
2) The motor operates according to the command from the
indoor controller.
Notes)
• When the fan rotates while the air conditioner stops due to
entering of outside air, etc, the air conditioner may operate
while the fan motor stops.
• When a fan lock is found, the air conditioner stops, and a
trouble is displayed.
1)
21
Drain pump delay
operation
When a cooling operation (including dry operation) is
stopped, the drain pump continues operating for 5 minutes
to reduce drain water in drain pan.
Turn on
SAVE
button on the remote controller.
2) During operation of save operation,
SAVE
lights on the
wired remote controller.
3) During power save operation, the current release control
is performed with the restriction ratio set in EEPROM on
the outdoor unit.
4) The restriction ratio can be set by keeping
SAVE
button
pushed for 4 seconds or more on the remote controller.
5) When validating the power save operation, the next
operation starts with power save operation valid because
contents are held even when operation stops, operation
mode changes or power supply is reset.
6) The restriction ratio can be set by changing the setup
data of CODE No. (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
Remarks
Check code [P12]
Operation and display
also are unavailable on
the wired remote
controller RBC-
AMT31E and before.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
For the setup operation,
refer to "Power saving
mode" of Installation
Manual.