– 79 –
DN
Item
Description
At shipment
F6
Presence of Application
control kit
(TCB-PCUC1E-1)
0000: None
0001: Exist
0000: None
d0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid
0001: Valid
0001: Valid
E6
Wireless remote
controller A-B selection
0000: A
0001: B
0000: A
b7
Occupancy sensor
operation at absent time
0000: Stand by
0001: operation stop
0000: Stand by
F0 Swing mode
0001 : Standard
000
3
: Cycle swing
0002 : Dual swing
0001: Standard
F1
Louver fixed position
(Louver No.1)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F2
Louver fixed position
(Louver No.2)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F
3
Louver fixed position
(Louver No.
3
)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F4
Louver fixed position
(Louver No.4)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed