Rear cabinet
Flange nut
Loosen the nut by turning
clockwise
Propeller fan
Fan
motor
No.
5
6
Part name
Rear cabinet
Fan motor
Procedure
1)
Perform works of items 1 of
1
and
2
.
2)
Take off the flange nut fixing the fan motor
and the propeller.
•
Turning it clockwise, the flange nut can be
loosened. (To tighten the flange nut, turn
counterclockwise.)
3) Remove the propeller fan.
4) Disconnect the connector for fan motor from
the inverter.
5) Take off the fixing screws (3 pcs.) holding by
hands so that the fan motor does not fall.
NOTE:
Tighten the flange nut with torque 4.9Nm
(50kgf/cm).
Remarks
1)
Perform works of items 1 of
1
and
2
,
3
.
2)
Take off fixed screws for the bottom plate.
(ST1T
Ø4
×
10
L, 2 pcs.)
3)
Take off fixed screw for the valve mounting
plate. (ST1T Ø4
×
10
L,
2
pcs.)
FILE NO. SVM-18042
–
80
–
Содержание RAV-GM301ATJP-E
Страница 20: ... 20 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM301AT P GM401AT P FILE NO SVM 18042 ...
Страница 24: ... 24 4 WIRING DIAGRAM 4 RAV GM301AT P GM401AT P FILE NO SVM 18042 ...
Страница 100: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...