2
6
–
This air conditioner adopted the
R32
refrigerant
which does not damage the ozone layer.
The working pressure of the refrigerant R
32
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and existing refrigerant or
refrigerating oil are not entered in the refrigerant
cycle of the air conditioner using the
new
refrigerant
during installation work or servicing time.
The next section describes the precautions for air
conditioner using the refrigerant.
Conforming to contents of the next section together
with the general cautions included in this manual,
perform the correct and safe work.
6-1.
Safety During Installation/Servicing
As R
32
’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and
materials exclusive for R
32
, it is necessary to
carry
out installation/servicing safely while taking
the
following precautions into consideration.
1.
Never use refrigerant other than R
32
in an air
conditioner which is designed to operate with
R
32
.
If other refrigerant than R
32
is mixed,
pressure in
the refrigeration cycle becomes
abnormally high,
and it may cause personal
injury, etc. by a
rupture.
2.
Confirm the used refrigerant name, and use
tools
and materials exclusive for the refrigerant
R
32
.
The refrigerant name R
32
is indicated on the
visible place of the outdoor unit of the air
conditioner using R
32
as refrigerant.
A diameter of charge port for R32 is the same as
that of the R410's Be careful not to charge the
refrigerant by mistake.
3.
If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
If
the refrigerant gas comes into contact with fire,
a
poisonous gas may occur.
4.
When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle.
Otherwise, pressure in the refrigeration cycle
may become abnormally high so that a rupture
or
personal injury may be caused.
5.
After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal level.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal level, an
oxygen starvation accident may result.
7. Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair may result in water leakage,
electric shock and fire, etc.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used.
Copper pipes and joints suitable for the refrigerant
must be chosen and installed.
Furthermore, it is necessary to use clean copper
pipes and joints whose interior surfaces are less
affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m.
Do not use copper pipes having a collapsed,
deformed or discolored portion (especially on
the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R
32
incurs pres-sure
higher than when using R22, it is necessary
to
choose adequate materials.
Thicknesses of copper pipes used with R
32
are
as shown in Table 6-2-1. Never use copper
pipes
thinner than 0.8mm even when it is avail-able on
the market.
NOTE:
Refer to the “
6-6. Instructions for Re-use Piping
of R22 or R407C
”.
6. REFRIGERANT R
32
SVM-13072.indb 29
SVM-13072.indb 29
11/01/13 1:53 PM
11/01/13 1:53 PM
FILE NO. SVM-18042
-1
Содержание RAV-GM301ATJP-E
Страница 20: ... 20 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM301AT P GM401AT P FILE NO SVM 18042 ...
Страница 24: ... 24 4 WIRING DIAGRAM 4 RAV GM301AT P GM401AT P FILE NO SVM 18042 ...
Страница 100: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...