Contents Error Display
*
When fixations of the errors were overlapped, the latest error is displayed.
ۑ
: ON
ە
: OFF
۔
: Rapid flash (5 times /sec.)
*
The LEDs are located at the top right of the P.C.
board of the outdoor unit as shown in the figure
on
the right.
FILE NO.SVM-18044
-1
- 51 -
ITEM
No.
LED
Display
D800
D801
D802
D803
D804
D805
1
Normal
2
Discharge temperature sensor (TD) error
3
Heat exchanger temperature sensor (TE) error
4
Heat exchanger temperature sensor (TL) error
5
Outside air temperature sensor (TO) error
6
Suction temperature sensor (TS) error
7
Heat sink temperature sensor (TH) error
8
Heat exchanger sensor (TE, TS) connecting error
9
EEPROM error
10
Compressor breakdown
11
Compressor lock
12
Current detection circuit error
13
Thermostat for compressor activated
14
Model data not set
15
MCU-MCU commumication error
16
Discharge temperature error
17
High pressure SW error
18
Power supply voltage error
19
Heat sink overheating error
20
Gas leak detected
21
4-way valve reverse error
22
High pressure release operation
23
Fan system error
24
Short-circuit of compressor drive element
25
Position detection circuit error
26
Compressor IPDU or other (not specially identifi ed)
27
Power supply error
Check code
[
W
i
r
e
d remote
controller]
F04
F06
F07
F08
F12
F13
F15
F31
H01
H02
H03
H04
L10
L29
P03
P04
P05
P07
P15
P19
P20
P22
P2
6
P29
-
-
D800 D801 D802 D803 D804 D805
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (Green)
Inspection window
through which to
check the LED
displays
Electric parts cover
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (
Green
)