1. Remove the front panel.
Pull and lift up front panel until it stops, move arms on left and right side
to outward direction then pull toward you to remove front panel.
Beware front panel fall down that may cause of injure or part damage.
2. Remove the terminal cover and cord clamp.
3. Insert the cable (according to the local cords) into the pipe hole on the
wall.
4. Take out the cable protrudes about 20 cm from the front.
5. Insert the cable fully into the terminal block and secure it tightly with
screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the cable with the cord clamp.
8. Fix the terminal cover and attach front panel to the indoor unit.
10-
4
-1. Wiring Connection
Indoor unit
Wiring of the cable can be carried out without removing the main panel.
Carry out attaching in the reverse order to removal.
Keep front panel horizontally and put both arms into guides.
Make sure both arms are inserted completely.
If the gap between main panel and front panel isn’t even, remove and
attach again.
How to attach the front panel
10-
4
. Electrical works
• Check local electrical cords and also any specifi c wiring instructions or
• Be sure to refer to the wiring system diagram labeled inside the
main panel.
limitations.
CAUTION
Fig. 10-
4
-
1
Fig. 10-
4
-
2
Fig. 10-
4
-
3
Model
50Hz, 220 – 240 V Single phase
Power source
Maximum running current
Circuit breaker rating
*
*
*
*
Power supply cable
Connecting cable
H07RN-F or 60245 IEC66 (1.5 mm
2
or more)
RAS-M10PKVPG-E
RAS-M13PKVPG-E
Front panel
Main panel
Front panel
*
*
RAS-M16PKVPG-E
Arm
Arm
Cable
about 20 cm
Terminals block