FILE NO. SVM-1
5006
7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19 35/-
B
10
N3
KV
2-E
1
0.9 to 1.1 12 to 14 37 to 39 High
High
49
0.8 to 1.0 11 to 13 46 to 48 High High
75
condition(°C)
Tempeature
Heat exchanger
pipe temp.
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/- 7/6
2.5 to 2.7 39 to 41 0 to 3 High High
60
2.6 to 2.8 41 to 43 0 to 2 High High
80
condition(°C)
Tempeature
Heat exchanger
pipe temp.
B
1
3N3
KV
2-E
1
B
10
N3
KV
2-E
1
B
1
3N3
KV
2-E
1
B
16
N3
KV2-E
1
0.8 to 1.0 11 to 13 40 to 42 High
High
71
2.7 to 2.9 43 to 45 0 to 2 High
High
72
B
16
N3
KV2-E
1