FILE NO. SVM-1
5006
2. SPECIFICATIONS
Unit model
Indoor
RAS-B10N3KV2-E
1
RAS-B13N3KV2-E
1
Outdoor
RAS-10N3AV2-E
1
RAS-13N3AV2-E
1
Cooling capacity
(kW)
2.5
3.5
Cooling capacity range
(kW)
1.1-3.1
1.1
-4.
05
Heating capacity
(kW)
3.2
4.2
Heating capacity range
(kW)
0.9-4.8
1.0
-5.
3
Power supply
Electric
Indoor
Operation mode
Cooling
Heating
Cooling
Heating
characteristic
Running current
(A)
0.21-0.19
0.24-0.22
0.21-0.19
0.24-0.22
Power consumption
(W)
35
40
35
40
Power factor
(%)
7
76
6
76
76
Outdoor
Operation mode
Cooling
Heating
Cooling
Heating
Running current
(A) 2.
94
-2.
71
3.
52
-3.
23
5.03
-4.
61
2.31
-4.
78
Power consumption
(W)
563
710
1015
1040
Power factor
(%)
87
9
2
9
2
9
1
Starting current
(A)
3.
76
5.17
COP (Cooling / Heating)
Operating
Indoor
High
(Cooling / Heating)
(dB-A)
38/39
39/40
noise
Medium
(Cooling / Heating)
(dB-A)
33/34
33/34
Low
(Cooling / Heating)
(dB-A)
26/28
26/28
Outdoor
(Cooling / Heating) (dB-A)
46/47
48/50
Indoor unit
Unit model
RAS-B10N3KV2-E
1
RAS-B13N3KV2-E
1
Dimension
Height
(mm)
275
275
Width
(mm)
790
790
Depth
(mm)
2
17
2
17
Net weight
(kg)
10
10
Fan motor output
(W)
20
20
Air flow rate
(Cooling / Heating) (m
3
/
/
min)
8.6/9.5
9.5/10.4
Outdoor unit Unit model
RAS-10N3AV2-E
1
RAS-13N3AV2-E
1
Dimension
Height
(mm)
550
550
Width
(mm)
780
780
Depth
(mm)
290
290
Net weigh
(kg)
33
33
Compressor
Motor output
(W)
750
750
Type
Twin rotary type with DC-inverter variable speed control to
s
ingle rotary type with DC-inverter variable speed control
Model
ASM89D16UFZ
Fan motor output
(W)
Air flow rate
(Cooling / Heating) (m
3
min)
30/30
37.5/37.5
Piping
Type
Flare connection
Flare connection
connection
Indoor unit
Liquid side
(mm)
∅
6.35
∅
6.35
Gas side
(mm)
∅
9.52
∅
9.52
Outdoor unit Liquid side
(mm)
∅
6.35
∅
6.35
Gas side
(mm)
∅
9.52
∅
9.52
Maximum length
(m)
20
20
Maximum charge-less length
(m)
15
15
Maximum height difference
(m)
10
10
Refrigerant
Name of refrigerant
R410A
R410A
Weight
(kg)
0.80
0.80
Wiring
Power supply
connection
Interconnection
Usable temperature range
Indoor
(Cooling / Heating)
(
o
C)
21-32/0-28
21-32/0-28
Outdoor
(Cooling / Heating)
(
o
C)
-10-46/-15-24
-10-46/-15-24
Accessory
Indoor unit
Installation plate
1
1
Wireless remote controller
1
1
batteries
2
2
Remote controller holder
1
1
TOSHIBA IAQ filer (long type)
1
1
Mounting screw
6 (
∅
4 x 25L)
6 (
∅
4 x 25L)
Pan head wood screw
2 (
∅
3
.
1 x 16L)
2 (
∅
3
.
1 x 16L)
Plasma air purifier
-
-
Installation manual
1
1
Owner's manual
1
1
Outdoor unit
Drain nipple
1
1
Water proof rubber cap
2
2
* The specification may be subject to change without notice for purpose of improvement.
43
1Ph/50Hz/220-240V , 1Ph/60Hz/220
-230
V
4.18/4.27
3.
33
/3.
89
3 Wires: Includes earth (Outdoor)
4 Wires: Includes earth
–
5
–
2-1. Specification