Installation Location

• A place which can bear the weight of the outdoor unit and does not cause 

an increase in noise level and vibration.

• A place where the operation noise and air discharge do not disturb 

neighbours.

• A place which is not exposed to strong wind.
• A place free of combustible gas.
• A place which does not block a passageway.
• A place where the drain water does not cause any problems.
• A place where there are no obstructions near its air intake or air outlet.

„

Precautions for Installation

• When the outdoor unit is to be installed in an elevated position, be sure to 

secure its feet.

• If the outdoor unit is to be mounted on a wall, make sure the base plate 

supporting it is sturdy enough.

• The base plate should be designed and manufactured to maintain its 

strength over a long d of time, and sufficient consideration should be given 
to ensure that the outdoor unit will not fall.

• When the outdoor unit is installed in a place that is always exposed to 

strong wind such as a coastal area or on a high story of a building, secure 
the normal fan operation using a duct or a wind shield.

• Especially in windy areas, install the unit in such a way as to prevent the 

admission of wind.

• When the outdoor unit is to be mounted high on a wall, take particular care 

to ensure that parts do not fall, and that the installer is protected.

• When doing installation work at ground level, it is usual to make wiring and 

pipe connections to the indoor units first, and then to make connections to 
the outdoor units.
However, if outdoor work is difficult you can change the procedure.
For example, by making adjustments to the wiring and piping lengths on the 
inside (rather than the outside).

Necessary Space for Installation

If you need to install the outdoor unit in a location where there are some 
obstructions or a wall, secure sufficient space as shown in the figure below.
The cooling/heating effect may be reduced by 10%.

Draining Off the Water from the Outdoor Unit

Install 5 waterproof rubber caps and the drain nipple to drain off the water 
from the outdoor unit.

• Seal the knock-out holes and screw/thread areas tightly using a silicon 

adhesive or a caulking compound.

• Use a drain pan to apply a centralized drain.

Installation in Regions with Snowfall and Cold Temperatures

Do not use waterproof rubber caps or a drain nipple.

• If you need to install the outdoor unit in a location where there is a possibility 

of the drain freezing, pay close attention so that the drain does not become 
frozen.

• To protect the outdoor unit from snow, install the outdoor unit on a holding 

frame, and attach a snow protection hood and plate.

• Keep the outdoor unit at least 500mm above the snow accumulation line.

Fixing the Outdoor Unit

Fix the outdoor unit using attachment bolts.

• Use 8mm or 10mm anchor bolts and nuts.
• Do not allow the attachment bolts to protrude by more than 15mm.
• Install the outdoor unit at ground level.
• Attach the vibration-proof rubber pads under the fixing legs.

Installation in the following places may result in trouble:
• A place with a lot of machine oil.
• A place with saline-rich atmosphere such as a coastal area.
• A place with high level of sulfide gas.
• A place where high-frequency waves are likely to be generated, such as 

from audio equipment, welders, or medical equipment.

Do not install the unit in such places.

150

 o

r mo

re

Upper side view (Unit: mm)

20

0 o

more

150 or more

300 or more

50

0 o

r mo

re

15

0 o

more

10

00 or

 

more

Side view (Unit: mm)

150 or 

more

500 or more

1000 or more

1000 or

 mor

e

GOOD

BAD

Water-proofing rubber cap

Drain nipple

Snow protection plate

Snow protection hood

At least 500 mm

Snow accumulation line

Holding frame

Anchor bolts

Front

Drain hole

Drain nipple mounting hole

Drain hole

150

525

45

600

400

365

150

15 mm or 

less

Mounting leg

Absorb vibration 

with vibration-proof 

rubber pads

Foundation

Foundation

If only the end 

of the 

mounting leg 

is supported, 

it may 

deform.

Do not support 

the outdoor unit 

only with the 

mounting leg.

Foundation

Bottom plate of 

outdoor unit

Support the bottom surface of the 

mounting leg that is in contact with 

and underneath the bottom plate of 

the outdoor unit.

+00EG44206701_01EN.book  Page 4  Tuesday, July 20, 2010  9:32 PM

Содержание RAS-5M34UAV-E1

Страница 1: ...Model name RAS 5M34UAV E1 Installation Manual Installation Manual Outdoor Unit 2 English For OUTDOOR USE only Manuel du proprietaire Unité hydroélectrique 16 Français Betriebsanleitung Wassergerät 30 Deutsch Installation Manual Outdoor Unit English ...

Страница 2: ...ONE LAYER R410A refrigerant is apt to be affected by impurities such as water oxidizing membranes and oils because the pressure of R410A refrigerant is approx 1 6 times of refrigerant R22 As well as the adoption of this new refrigerant refrigerating machine oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating machine oil does not ...

Страница 3: ...sed it may cause overpressure and result in compressor damage At the same time if there is a leak in the connection part it may cause air suction and overpressure resulting in burst or injury The following must be certainly done during pump down Do not incorporate air into the refrigeration cycle Close the 2 service valves Stop the compressor and remove the refrigerant pipe If the refrigerant pipe...

Страница 4: ...me DAISEIKAI 5 DFS 1 DFS 2 class abbreviation 10 13 16 18 10 13 16 18 07 10 13 16 22 24 10 13 16 10 13 16 10 13 18 Model name RAS M10PKVP E RAS M13PKVP E RAS M16PKVP E RAS M18PKVP E RAS M10PKVP ND RAS M13PKVP ND RAS M16PKVP ND RAS M18PKVP ND RAS M07SKV E RAS M10SKV E RAS M13SKV E RAS M16SKV E RAS M22SKV E RAS M24SKV E RAS M10GDV E RAS M13GDV E RAS M16GDV E RAS M10SMUV E RAS M13SMUV E RAS M16SMUV E...

Страница 5: ...e Water from the Outdoor Unit Install 5 waterproof rubber caps and the drain nipple to drain off the water from the outdoor unit Seal the knock out holes and screw thread areas tightly using a silicon adhesive or a caulking compound Use a drain pan to apply a centralized drain Installation in Regions with Snowfall and Cold Temperatures Do not use waterproof rubber caps or a drain nipple If you nee...

Страница 6: ... in then tighten the nut If you find air is not taken in make sure that the charge hose is connected to the port s securely Perform extraction for about 40 minutes and make sure that the compound pressure gauge reading is 101kPa 76cmHg If the compound pressure gauge reading is not 101kPa 76cmHg there is a possibility air is being taken in from the port s Make sure that the charge hose is connected...

Страница 7: ...Leak Inspection Perform a gas leak inspection for the flare nut connections valve stem connection and service port cap without fail Use a leak detector exclusively manufactured for R410A Performing Additional Installation of an Indoor Unit 1 Collect refrigerant from the outdoor unit 2 Turn off the circuit breaker 3 Perform additional installation referring to the procedure from Refrigerant Piping ...

Страница 8: ...ion may cause a failure 1 Detach the front panel from the outdoor unit 2 Remove the cord clamp 3 Connect the wires for the power source and each indoor unit Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 4 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 5 At...

Страница 9: ...ed to the other units When you start running the indoor unit or change the operation mode the unit starts running after 3 minutes This is due to the protection function of the unit not a malfunction When the external temperature becomes low the pre heating of the compressor starts to protect it Keep the circuit breaker on for use The electricity consumption during pre heating is about 100W If the ...

Страница 10: ...EG44206701 ...

Отзывы: