Code
Fault Description
P05 01
Phase-missing detection (series 1 & 2) or High D.C. inverter voltage (series 4). Detected at outdoor. Fault Code is outdoor model series specific e.g.
MMY-MAP###
1
HT8-E, MMY-AP###
2
HT8-E or MMY-MAP###
4
HT8-E therefore example fault code for P0501 will be (MMY-MAP0801HT8-E (
series 1
),
MMY-MAP0802HT8-E (
series 2
), MMY-MAP0804HT8-E (
series 4
) s
earch
P05011, P05012 or P05014
P05 01
1
Phase-missing detection. Detected at outdoor. Likely cause error on power supply to condenser
P05 01
2
Phase-missing detection. Detected at outdoor. Likely cause error on power supply to condenser
P05 01
4
High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 1 IPDU board overheat or failure
P05 02
Phase-order incorrect (series 1 & 2) or High D.C. inverter voltage (series 4). Detected at outdoor. Fault Code is outdoor model series specific e.g. MMY-
MAP###
1
HT8-E, MMY-AP###
2
HT8-E or MMY-MAP###
4
HT8-E therefore example fault code for P0502 will be (MMY-MAP0801HT8-E (
series 1
), MMY-
MAP0802HT8-E (
series 2
), MMY-MAP0804HT8-E (
series 4
) s
earch
P05011, P05012 or P05014
P05 02
1
Phase-order incorrect. Detected at outdoor. Likely cause issue with power supply to condenser, swap L2 & L3 to correct
P05 02
2
Phase-order incorrect. Detected at outdoor. Likely cause issue with power supply to condenser, swap L2 & L3 to correct
P05 02
4
High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 2 IPDU board overheat or failure
P05 03
High D.C. inverter voltage. Detected at outdoor. Likely cause compressor 3 IPDU board overheat or failure
P07
Overheating compressor IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU. Fault sub code
required to determine which IPDU overheated 01=IPDU1 02=IPDU2 03=IPDU3. Retrieve fault sub-code from condenser interface PCB by placing
rotary dials to position 1 / 1 / 1 for diagnosis.
P07 01
Overheating compressor 1 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 1
P07 02
Overheating compressor 2 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 2
P07 03
Overheating compressor 3 IPDU / inverter board. Detected at outdoor. Likely cause poorly secured inverter PCB to heat-sink, faulty IPDU board 3
P10
Indoor float switch open circuit as result of high condensation levels within drip tray, detected indoors. Likely cause faulty float switch, faulty lift pump,
debris blocking drain
P12
Indoor fan motor trouble. Detected indoors. Likely cause fan motor locked, incorrectly configured PCB, indoor PCB fault
P13
Outdoor liquid back detection in condenser while in OFF cycle. Detected at outdoor. Likely cause increase in pressure within dormant condenser,
possible PMV valves passing
P15
High compressor suction or discharge temperature. Detected at outdoor. Likely cause sensor condition (TS1 or TD1, 2 or 3), interface PCB fault, loss of
refrigerant TS1 sensor value 20°c=12.5k ohms TD1,2 & 3 sensor value 20°c=63k ohms. Retrieve fault sub-code from condenser interface PCB by
placing rotary dials to position 1 / 1 / 1 for diagnosis.
P15 01
High compressor suction temperature. Detected at outdoor. Likely cause suction sensor condition (TS1), interface PCB fault, loss of refrigerant sensor
value 20°c=12.5k ohms
P15 02
High compressor discharge temperature. Detected at outdoor. Likely cause discharge sensor condition (TD1, TD2 or TD3), interface PCB fault, loss of
refrigerant sensor value 20°c=63k ohms
P17
High compressor discharge temperature. Detected at outdoor. by TD2 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows & TD2
sensor condition sensor value 20°c=63k ohms
P18
High compressor discharge temperature. Detected at outdoor. by TD3 @ 115°c. Likely cause low refrigerant, poor refrigerant flow and airflows & TD3
sensor condition sensor value 20°c=63k ohms
P19
Incorrect temperature / pressure reading at condenser. Detected at outdoor. Likely cause check characteristics of pressure transducers (PS & Pd) and
temperature sensors (TS1, TE1 & TL), interface PCB fault sensor value 20°c=12.5k ohms