Stopped because of error of other indoor unit in a group
(Check codes of E03/L03/L07/L08)
Outdoor unit: Outdoor unit error
Protective device of
Outdoor unit: Inverter Idc operation
∗
1
Outdoor unit: Position detection error
outdoor unit worked.
Outdoor unit high pressure protection
4-way valve system error (Indoor or outdoor unit judged.)
Negative phase detection error
Heat sink overheat error
Outdoor unit error
Gas leak detection error
Outdoor unit discharge temp. error
Protective device of
∗
1
Outdoor high pressure system error
outdoor unit worked.
Overflow was detected.
Protective device of indoor unit worked.
Indoor DC fan error
Miswiring between indoor unit and outdoor unit or connection erorr
(Communication stop between indoor and outdoor units)
Wire connection error between indoor units, Indoor power OFF
(Communication stop between indoor master and follower or between main
and sub indoor twin)
Communication error between CPUs on indoor unit P.C. board
Duplicated indoor unit No.
Setup error
Duplicated master units of remote controller
Receiving error
Receiving unit
Miswiring or wire connection error
Sending error
Communication stop
between receiving unit and indoor unit
Power supply OFF or miswiring between receiving unit and indoor unit
P31
Cause of trouble occurrence
P29
P26
P22
P20
P19
P15
P07
P05
P04
P03
P12
P10
E04
E18
E10
E09
E08
E03
E02
E01
—
Alternate flash
Check code
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Flash
Operation Timer
Ready
No indication at all
Operation Timer
Ready
: Flash (0.5 sec.)
: Go on,
: Go off,
Lamp indication
Lamp indication
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Check code
F01
F02
P10
F04
F06
F07
F08
F12
F13
F15
F29
F31
H01
H02
H03
H04
H06
L03
L07
L08
L09
L10
L20
L29
L30
L31
Cause of trouble occurrence
Heat exchanger sensor (TCJ) error
Heat exchanger sensor (TC) error
Indoor unit sensor error
Heat exchanger sensor (TA) error
Discharge temp. sensor (TD) error
Temp. sensor (TE) error
Temp. sensor (TL) error
Temp. sensor (TO) error
Sensor error of outdoor unit
∗
1
Temp. sensor (TS) error
Temp. sensor (TH) error
Temp. Sensor miswiring (TE, TS)
Indoor EEPROM error
Outdoor EEPROM error
Compressor break down
Compressor lock
Current detection circuit error
Outdoor compressor system error
∗
1
Case thermostat worked.
Outdoor unit low pressure system error
Duplicated master indoor units
There is indoor unit of group connection
→
AUTO address
in individual indoor unit.
* If group construction and
Unsetting of group address
address are not normal
Missed setting
when power supply turned on,
(Unset indoor capacity)
automatically goes to address
setup mode.
Unset model type (Service board)
Duplicated indoor central addresses
Outdoor unit and other error
Others
Outside interlock error
Negative phase error
Operation
Timer
Ready
Simultaneous flash
Operation
Timer
Ready
Alternate flash
—
—
During test run
Disagreement of cool/heat
(Automatic cool/heat setting to automatic cool/heat prohibited
model, or
setting of heating to cooling-only model)
Page
25
of
7
8
Indoor Lamp Indication for Trouble Shooting -
RAV Series