– 41 –
Outdoor Unit : RAS-4M27GAV-E
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 meters × 4 units (5m/each indoor unit)
Temperature
condition
Operating combination
(Unit)
Heat exchanger
pipe temp.
Indoor
Outdoor
No. of
operating
units
A
B
C
D
Standard
pressure
P (MPa)
T1 (°C)
T2 (°C)
Indoor
fan
Outdoor
fan
Compressor
revolution
(rps)
10
–
–
–
2.7 to 2.9
44 to 46
2 to 4
High
MED
41
13
–
–
–
3.2 to 3.4
52 to 54
2 to 4
High
MED
52
1 unit
16
–
–
–
3.6 to 3.9
53 to 55
2 to 4
High
MED
56
10
10
–
–
2.7 to 2.9
45 to 47
0 to 2
High
MED
62
13
10
–
–
2.8 to 3.0
45 to 47
0 to 2
High
MED
64
16
10
–
–
2.9 to 3.1
46 to 48
0 to 2
High
MED
66
13
13
–
–
2.9 to 3.1
46 to 48
0 to 2
High
MED
67
16
13
–
–
3.0 to 3.2
47 to 49
–1 to 1
High
MED
69
2 units
16
16
–
–
3.1 to 3.3
48 to 50
–1 to 1
High
MED
71
10
10
10
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
72
13
10
10
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
72
16
10
10
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
72
13
13
10
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
16
13
10
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
13
13
13
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
16
16
10
–
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
16
13
13
–
2.5 to 2.7
37 to 39
–2 to 0
High
MED
74
16
16
13
–
2.5 to 2.7
37 to 39
–2 to 0
High
MED
74
3 units
16
16
16
–
2.5 to 2.7
37 to 39
–2 to 0
High
MED
74
10
10
10
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
72
13
10
10
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
72
16
10
10
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
73
13
13
10
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
73
16
13
10
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
73
13
13
13
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
73
16
13
13
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
74
20 / –
7 / 6
4 units
16
16
10
10
2.0 to 2.2
33 to 35
–2 to 0
High
MED
74