– 37 –
7. REFRIGERANT CYCLE DIAGRAM
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E / RAS-4M27GAV-E
NOTE :
• The maximum pipe length of this air conditioner is 70 m. The additional charging of refrigerant is unnecesary
because this conditioner is designed with charge-less specification.
• Connection of only one indoor unit is unavailable. Two or more indoor units should be connected.
To
D room
To
C room
To
B room
To
D room
Indoor unit A
T1
TCa
Connecting pipe
Thickness : 0.8mm
Ø12.7 :
RAS-B16GKVP-E
Ø9.52 :
RAS-B10GKVP-E
RAS-B13GKVP-E
Allo
w
a
b
le height
diff
erence :
15m
Allo
w
a
b
le pipe length
Evaporator
Cross flow fan
To
C room
To
B room
P
T2
TO
Propeller fan
Outdoor unit
TA
TD
TGa
Strainer
Packed valve (Gas side)
(Ø12.7)
Accumulating
tank 1500cc
Compressor
DA220A2F-20L
Muffler
Ø25 x 160L
Packed valve (Liquid side)
(Ø9.52)
TGd
TGc
TGb
Per 1 unit
Max. : 25m
Min. : 2m
Total
Max. : 70m
(Ø6.35)
(Ø9.52) (Ø9.52) (Ø9.52) (Ø12.7)
(Ø6.35) (Ø6.35) (Ø6.35)
Pulse motor
valve at liquid side
(UKV-18D)
Refrigerant amount : 2.4kg (R410A)
NOTE : Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
Temp. measurement
Pressure
measurement
Gauge attaching port
Vacuum pump
connecting port
Sectional shape
of heat insulator
Connecting pipe
Thickness : 0.8mm
Ø6.35
Temp. measurement
TS
TE