– 7 –
• For performance when each indoor unit is combined with other unit, refer to the separate table.
• The specifications may be subject to change without notice for purpose of improvement.
<Cooling Only Models>
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E / RAS-4M27GACV-E
Indoor
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E
Unit model
Outdoor
RAS-4M27GACV-E
Cooling capacity
(kW)
8.0
Cooling capacity range
(kW)
1.4 – 9.2
Heating capacity
(kW)
—
Heating capacity range
(kW)
—
Power supply
220–240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz
Unit model
RAS-M10GKCVP-E
RAS-M13GKCVP-E
RAS-M16GKCVP-E
Running current
(A)
0.15
0.15
0.15
Power consumption
(W)
30
30
30
Indoor
Power factor
(%)
91/87/83
91/87/83
91/87/83
Unit model
RAS-4M27GACV-E
Running current
(A)
11.60/11.09/10.63
Power consumption
(W)
2500
Power factor
(%)
98
Electric
characteristics
Outdoor
Starting current
(A)
11.60/11.09/10.63
COP
3.20
Unit model
RAS-M10GKCVP-E
RAS-M13GKCVP-E
RAS-M16GKCVP-E
High
(dB•A)
42
43
45
Medium
(dB•A)
33
34
36
Indoor
Low
(dB•A)
27
27
29
Unit model
RAS-4M27GACV-E
Operating
noise
Outdoor
Full indoor units operating
(dB•A)
48
Unit model
RAS-M10GKCVP-E
RAS-M13GKCVP-E
RAS-M16GKCVP-E
Height
(mm)
250
250
250
Width
(mm)
790
790
790
Dimension
Depth
(mm)
215
215
215
Net weight
(kg)
9
9
9
Fan motor output
(W)
30
30
30
Indoor unit
Air flow rate
(m³/h)
550
560
640
Unit model
RAS-4M27GACV-E
Height
(mm)
795
Width
(mm)
900
Dimension
Depth
(mm)
320
Net weight
(kg)
63
Motor output
(W)
2000
Type
Twin rotary type with DC-inverter variable speed control
Compressor
Model
DA220A2F-20L
Fan motor output
(W)
60
Air flow rate
(m³/h)
High : 3000, Medium : 2800
Outdoor unit
Type
Flare connection
Unit model
RAS-M10GKCVP-E
RAS-M13GKCVP-E
RAS-M16GKCVP-E
Indoor unit
Liquid side/Gas side
Ø6.35/ Ø9.52
Ø6.35/ Ø9.52
Ø6.35/ Ø12.7
Unit model
RAS-4M27GACV-E
A unit liquid side/Gas side
Ø6.35/ Ø12.7
B unit liquid side/Gas side
Ø6.35/ Ø9.52
C unit liquid side/Gas side
Ø6.35/ Ø9.52
Outdoor unit
D unit liquid side/Gas side
Ø6.35/ Ø9.52
Maximum length (per unit)
(m)
25
Maximum length (total)
(m)
70
Maximum chargeless length
(m)
70
Maximum height difference
(m)
15
Name of refrigerant
R410A
Piping
connection
Weight
(kg)
2.2
Power supply
3 Wires : includes earth
Wiring connection
Interconnection
4 Wires : includes earth
Indoor
(°C)
21 to 32
Usable temperature range
Outdoor
(°C)
10 to 43
Unit model
RAS-M10GKCVP-E
RAS-M13GKCVP-E
RAS-M16GKCVP-E
Installation plate
1
1
1
Wireless remote controller
1
1
1
Batteries
2
2
2
Remote controller holder
1
1
1
Zeolite-plus filter
1
1
1
Plasma pure filter
1
1
1
Remote controller holder mounting screw
2 (Ø3.1 × 16L)
2 (Ø3.1 × 16L)
2 (Ø3.1 × 16L)
Owner’s manual
1
1
1
Mounting screw
6 (Ø4 × 25L)
6 (Ø4 × 25L)
6 (Ø4 × 25L)
Indoor unit
Installation manual
1
1
1
Unit model
RAS-4M27GACV-E
Installation manual
1
Accessory
Outdoor unit
Specifications
1
Содержание RAS-3M26GAV-E
Страница 121: ... 121 MCC 1438 ...