No.
Part name
Procedures
Remarks
"
TS sensor (Suction pipe temperature sensor)
• Attachment
Install the senser onto the straight pipe part of the suction pipe.
Be careful for the lead direction of the sensor.
#
TD sensor (Discharge pipe temperature sensor)
• Attachment
With its leads pointed upward, install the sensor onto the vertical straight
pipe part of the discharge pipe.
$
TO sensor (Outside air temperature sensor)
• Attachment
Insert the outdoor air temperature sensor into the holder, and install the
holder onto the heat exchanger.
CAUTION
During the installation work (and on its completion), take care not to damage the coverings of the sensor leads on the edges
of the metal plates or other parts. It is dangerous for these coverings to be damaged since damage may cause electric
shocks and/or a f re.
CAUTION
After replacing the parts, check whether the positions where the sensors were installed are the proper positions as
instructed. The product will not be controlled properly and trouble will result if the sensors have not been installed in their
proper positions.
FILE NO. SVM-19004
- 126 -
Содержание RAS-18J2AVG-EE
Страница 19: ...4 2 Outdoor Unit RAS 05 07 10 13J2AVG EE C L C L 280 400 Unit mm 280 300 FILE NO SVM 19004 19 ...
Страница 22: ...RAS 16J2KVG EE RAS 16J2AVG EE FILE NO SVM 19004 22 ...
Страница 23: ...RAS 18J2KVG EE RAS 18J2AVG EE FILE NO SVM 19004 23 ...
Страница 135: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...