– 8 –
FILE NO. SVM-06051
5. REFRIGERATING CYCLE DIAGRAM
Surface temp. of heat exchanger
Ambient temp. conditions
Conditions
interchanging pipe (
°
C)
DB/WB (
°
C)
T
1
T
2
Indoor
Outdoor
Standard 8 54 27/19.5 35/24
RAC-24G-AR High temperature 14 73 32/22.5 52/24
Low temperature -1 40 21/15.5 21/15.5
Standard 8 51 29/19 46/24
RAC-24G2B, 24GE2B, 24G2L High temperature 13 74 32/22.5 52/24
Low temperature
0
41
21/16
21/16
Note : Measure the heat exchanger temperature at the center of U-bend.
(By means of thermistor thermometer)
* When servicing the cycle, be sure to change the strainer for the dryer.
Evaporator
Suction Pipe
Compressor
Discharge Pipe
Condenser
Strainer (Dryer)
1.5
∅
x700L (1.5
∅
x1400L;G-AR)
Capillary Tube(Comp injection)
(1 pcs)
(1.0
∅
x700L)
1.5
∅
x900L (1.5
∅
x1400L;G-AR)
1.5
∅
x700L (1.5
∅
x1300L;G-AR)